Installation
48
FRONT DOOR OPENING
The door is adjusted in the factory with standard opening to the left (Sx) and hinges on the right (Dx).
a
DANGER
It is DANGEROUS TO UNSCREW the ferrules (8) on the side of the hinges. This may cause the door to detach, with
possible serious harm to people and property damage.
Check the correct adjustment of the tie-rods and hinges ensuring that, during closure, the seal gasket is evenly pressed in the
centre on the whole circumference. If necessary, adjust the door as described in the following paragraph.
FRONT DOOR ADJUSTMENT
a
DANGER
Incorrect door adjustment with consequent damage to people and property voids the warranty conditions.
DOOR ADJUSTMENT (OPENING ON THE RIGHT)
1
2
3
6
4
5
7
Dx
Sx
VERTICAL ADJUSTMENT
To make the adjustment:
–
with the door ajar, loosen the counter-nuts (1) of the hinge units
–
act on the adjustment nuts (2) to lift or lower the door by centring the gasket on the stop plate, then block the counter-nuts
(1)
–
close the door and centre the tie-rod (4) on the mechanical tube (5), proceeding as in the previous point.
HORIZONTAL ADJUSTMENT
Close the door using the lever and check that there is equal distance on both sides, between the stop plate and the band. If this
is not the case:
–
with the door ajar, loosen the locking nuts (6) of the hinge units
–
act on the ferrule (7) to adjust the distance depth-wise
–
screw the nuts (6) and block the conical washers on the mechanical tubes.
a
DANGER
When cross-changing ferrules, always make sure that the other two ferrules are fastened, so that they hold the door.
Check the proper adjustment in depth ensuring that the door, manually pushed up to the stop plate, naturally returns remaining
ajar. This is to ensure the hinge side fume seal.