Installation
25
HORIZONTAL ADJUSTMENT
Close the door using the lever and check that there is equal distance on both sides, between the stop plate and the band. If this
is not the case:
–
with the door ajar, loosen the locking nuts (6) of the hinge units
–
act on the ferrule (7) to adjust the distance depth-wise
–
screw the nuts (6) and block the conical washers on the mechanical tubes.
Sx
a
b
c
7
6
Sx
6
a
DANGER
When cross-changing ferrules, always make sure that the other two ferrules are fastened, so that they hold the door.
Check the proper adjustment in depth ensuring that the door, manually pushed
up to the stop plate, naturally returns remaining ajar. This is to ensure the hinge
side fume seal.
a
DANGER
THERE MUST BE NO FLUE GAS LEAKS.
TURBULATOR ASSEMBLY
To assemble the turbulators supplied with the boiler, open the door and insert the turbulators completely into the smoke pipes,
until they penetrate by at least 100 m.
a
DANGER
The turbulators have very pointed and sharp ends. Therefore, wear suitable protective gloves during insertion
(equipment according to current regulation).
100
mm
Data relevant to the size, diameter and length (ØxP) and to the quantities (no.) of the turbulators (Tb) for the various models are
listed in the table "
" present in the paragraph "
".
Cooke Industries - Phone: +64 9 579 2185 Email: sales@cookeindustries.co.nz Web: www.cookeindustries.co.nz