General information
9
TECHNICAL DATA
DESCRIPTION
u.m.
BNX
100
150
350
500
700
850
Effective rated
[1]
kW
69,8
105
233
349
465
581
Thermal capacity
kW
77,4
115
256
383
511
639
Efficiency at 100% (ref. P.C.I.)
[1]
%
90,00
91,00
91,00
91,00
91,00
91,00
Pressure drops on exhaust side
mbar
0,7
1,5
3,5
3,5
5,0
4,5
Rated pressure
bar
0,98
0,98
0,98
0,98
0,98
0,98
Total capacity
l
198
410
805
875
995
1400
Capacity at level
l
146
250
515
690
800
1100
Exchange surface
m
2
2,30
3,60
6,00
9,00
10,50
13,50
Steam production
[1]
kg/h
100
150
350
500
700
850
Rated frequency ~ voltage
Volt ~
Hz
1/N~ 230 ~ 50
1/N~ 230 ~ 50
1/N~ 230 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
Electric protection rating
IP
55
55
55
55
55
55
Absorbed electrical power
[2]
W
1500
1500
1500
6000
6000
6000
Allowed fuels
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Total weight
kg
470
660
1080
1300
1400
2000
DESCRIPTION
u.m.
BNX
1000
1400
1700
2000
2650
3000
Effective rated
[1]
kW
698
897
1163
1395
1744
2035
Thermal capacity
kW
767
985
1278
1533
1917
2236
Efficiency at 100% (ref. P.C.I.)
[1]
%
91,00
91,00
91,00
91,00
91,00
91,00
Pressure drops on exhaust side
mbar
6,0
5,5
7,0
7,5
6,5
7,5
Rated pressure
bar
0,98
0,98
0,98
0,98
0,98
0,98
Total capacity
l
1400
2010
2280
3020
4240
4240
Capacity at level
l
1100
1560
1790
2050
3100
3100
Exchange surface
m
2
15,50
22,00
26,00
31,00
42,00
46,00
Steam production
[1]
kg/h
1000
1350
1700
2000
2650
3000
Rated frequency ~ voltage
Volt ~
Hz
3/N~ 400 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
3/N~ 400 ~ 50
Electric protection rating
IP
55
55
55
55
55
55
Absorbed electrical power
[2]
W
6000
6000
9500
9500
12500
12500
Allowed fuels
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Methane -
LPG - Diesel
- Naphtha
Total weight
kg
2000
2500
2700
3600
4900
4900
[1]
Water delivery
80°C
.
[2]
Electric powers only for gas or diesel fuels.
Design data
Maximum/minimum temperature
-10°C / 120,1°C
Cooke Industries - Phone: +64 9 579 2185 Email: sales@cookeindustries.co.nz Web: www.cookeindustries.co.nz