PART III: OPERATION
34
MultiBloc MBE
Regulation VD-R whith PS
Pressure taps
MultiBloc MBE
Increasing pressure
Decreasing pressure
Fig. 2
Setting scale is „Not“ linear! Various sensors available.
Output pressure according to sensor‘s measuring
range.
Adjust the outlet pressure to the value specified by the
burner or equipment manufacturer!
While making outlet pressure adjustments, do not
exceed a value that creates a hazardous condition to the
burner!
Adjusting output pressure for positive pressure
systems (requires PS-10/40 or PS-50/200):
Outlet
pressure
MIN
10%
25%
50%
75%
MAX
PS-10/40
4 mbar
0,4 kPa
2 "w.c.
10 mbar
1,0 kPa
4 "w.c.
25 mbar
2,5 kPa
10 "w.c.
50 mbar
5,0 kPa
20 "w.c.
75 mbar
7,5 kPa
30 "w.c.
100 mbar
10,0 kPa
40 "w.c.
PS-50/200
20 mbar
2,0 kPa
8 "w.c.
50 mbar
5,0 kPa
20 "w.c.
125 mbar
12,5 kPa
50 "w.c.
250 mbar
25,0 kPa
100 "w.c.
375 mbar
37,5 kPa
150 "w.c.
500 mbar
50,0 kPa
200 "w.c.
ATTENTION:
To set the outlet pressure of the VD-R regulator, act on the adjustment ring nut (Fig. 10)
The position of the indicator in the dial indicates the value of the outlet pressure calculated as a percentage of the
full scale of the PS sensor (Fig. 11)
Fig. 3
10%
25%
50%
75%
Max.
Min.
1, 2, 3, 5
Sealing plug
4
For system accessories
Fig. 4
Summary of Contents for NEOX125
Page 45: ...Siemens LMV5x Manuale assistenza tecnica M12920AC rev 2 1 08 2017 ...
Page 56: ...12 2 2 LMV5x struttura dei menù ...
Page 83: ...39 ...
Page 90: ......
Page 91: ......
Page 94: ...Allegato 1 Esempio di cavo per motore ...
Page 95: ......
Page 96: ...Allegato 2 Esempio di cavo per sensori ...
Page 97: ......
Page 98: ......