17
22.
Relay Operation (dehumidification only)
Set the relay function to match your system (normally open, normally closed).
Press the
or
to select. Press
to advance to the next screen.
CONFIG
HUMIDITY
24.
Check Filter Timer
(
800-2500 hours
)
After the number of (fan running) hours specified, (for example, 1200 hours), the words
“CHECK FILTER” will display to remind you to check/change the system filter. The next
configuration screen is where the elapsed number of run hours can be reset.
Press the
or
to select. Press
to advance to the next screen.
CONFIG
Check
Filter
23.
Fan on Schedule
(OFF, WAKE, LEAVE, RETURN, SLEEP)
The fan will run continuously during this scheduled period when the mode is not set to OFF. To
turn on the fan during one of the scheduled periods (WAKE, LEAVE, RETURN, SLEEP), please
do the following:
Press the
or
to select. Press
to advance to the next screen.
CONFIG
ON
SCHEDULE
FAN
OFF
CONFIG
HUMIDITY
21.
Extended AC
(no, COOL -2 (Fahrenheit), COOL -1 (Celsius))
Note:
Only used for Dehumidification when condition is set to COOL-FAN
.
Set an extended time on the AC to increase dehumidification capabilities.
no
= No extended AC time.
COOL -2 or COOL -1
= Cooling system will continue to operate after the set temperature has
been reached until the room temperature is 3°F (1.5°C) below the set
temperature if dehumidification has not been satisfied.
Press
or
to select.
Press
to advance to the next screen.