22
Testing the Thermostat Humidity Control
Humidification Test
––
when set to humidification, only
To test the humidifier, set the mode and fan to the correct setting:
HEAT-FAN
: Either the heating system or fan must be operating in order for the humidifier to turn on.
HEAT
: Heat must be operating in order for the humidifier to turn on.
no
: No condition other than humidity reading below setpoint and differential will turn on humidifier.
1. Go to
MENU/HUMIDITY
and press
.
2. Change the humidity setpoint above the relative humidity by the differential (Configuration Menu, Section 19, Page 16).
3. Press
twice. You should hear a click and when you go back into the humidity settings you will see ON in the top left
corner of the screen.
4. Change the humidity setting below the relative humidity by the differential. The humidifier will turn off.
Dehumidification Test
––
when set to dehumidification, only
To test dehumidification, set the mode and fan to the correct settings.
COOL-FAN
: Either the cooling system or fan must be operating in order for the dehumidifier to turn on.
COOL-no:
The cooling system must be turned off in order for the dehumidifier to turn on.
no
: No condition other than humidity reading above setpoint and differential will turn on dehumidifier.
1. Go to
MENU/HUMIDITY
and press
.
2. Change the humidity setpoint below the relative humidity by the differential (Configuration Menu, Section 19, Page 16).
3. Press
twice. If the relay configuration is set to normally open, there will be a click and the humidity screen will display
ON. If the relay configuration is set to normally closed, the humidity screen will not display ON.
4. Change the humidity setting to greater than the relative humidity by the differential by pressing the
.
5. Press
twice. If the relay configuration is set to normally closed, there will be a click and ON is displayed on the humidity
screen. If the relay configuration is set to normally open, the humidity screen will not display ON.