9
* G not on for
gas/oil systems
2020HR Output Chart
1
ST
Cool
2
ND
Cool
1
ST
Heat
2
ND
Heat
Heat/Cool
Y1, G
Y1, Y2, G
W1, G*
W1, W2, G*
Heat Pump (One Compressor)
Y1, G, O
Y1, G, O
Y1, G, B
Y1, W2, G, B
Heat Pump (Two Compressors)
Y1, G, O
Y1, Y2, G, O
Y1, G, B
Y1, Y2, G, B
Emergency Heat (Heat Pump Only)
N/A
N/A
W2, G
N/A
1
ST
Cool
1
ST
Heat
2
ND
Heat
Heat/Cool
Y1, G
W1, G*
W1, W2, G*
Heat Pump (One Compressor)
Y1, G, O
Y1, G, B
Y1, G, B, W2
Emergency Heat (Heat Pump Only)
N/A
W2, G
N/A
2010HR Output Chart
* G not on for
gas/oil systems
1010HR Output Chart
1
ST
Cool
1
ST
Heat
Heat/Cool
Y1, G
W1, G*
Heat Pump (One Compressor)
Y1, G, O
Y, G, B
* G not on for
gas/oil systems
(De)humidification Setting
With Humidity Control Demand
No
N/A
Humidification
Only
Heat
W
Heat-Fan
W and/or G
Dehumidification
Only
Cool-No
G only
Cool-Fan
Y and/or G
Humidity Output Chart
Note:
When in dehumidification
mode and EAC is set to
Cool-2, Y2 will energize
to extend cooling cycle.
See Configuration menu
section 21, Page 17.