background image

Symptom

Problem

Fan overheats, over 

amps or runs very 

rough

Check with the motor manufacturer to see if the motor is able 

to be speed controlled by reducing the input voltage. Verify 

the motor is a single phase PSC motor.

The fan cycles from 

full ON to full OFF 

with little or no 

modulation

Check the Hard start  setting in the App. Too much  hard start 

can drop pressure too quick causing a fan cycling  effect. 

Lower the hard start in the App. 
Should the fan cycling  persist, move the probe up several 

bends into the condenser to increase the sensitivity to the 

condensing temperature.
Adjust the minimum output voltage in the  App while fine 

tuning the probe placement on the condenser.

The fan does not 

come on at all

Using an AC voltmeter, measure the voltage between the 24 

VAC terminals. It should read approximately 24 volts.
Measure the line voltage between LINE 1 and LINE 2 to confirm 

that line voltage is present. Check Line 1 of the ICM325A 

and confirm it is connected to the same leg of power as the 

common of the Run capacitor. 
Remove the thermistor probe from the terminal block and 

measure its resistance at ambient temperature. Compare your 

reading at the appropriate temperature in Appendix B to see 

if the actual resistance approximates the listed value. Next, 

hold the probe in your hand and confirm that the resistance 

decreases. If a pressure sensor is used, measure the DC 

voltage between GND and the sensor output at BWG and 

compare your reading to the expected pressure in Appendix A.

The high pressure 

switch trips off

Move the probe further into the condenser where the 

temperature is higher. This will produce a higher fan RPM and 

will decrease the head pressure.
Fine adjust the cutout and hard start settings in the App.

GREEN

AMBER

Condition

OFF

OFF

• No voltage at L1 or L2

• No control voltage when jumper is placed

• Output is off

ON

OFF

Full Speed Operation

OFF

ON

Variable Speed Operation

OFF

2 Flashes

Shorted Sensor (Temperature or Pressure)

OFF

3 Flashes

Open Sensor (Temperature or Pressure)

TROUBLESHOOTING

LED DIAGNOSTIC INDICATORS

APPENDIX A

APPENDIX B

TEMPERATURE VS. PROBE RESISTANCE

°C

°F

Resistance (KΩ)

32°

32.7

41°

25.4

10°

50°

19.9

15°

59°

15.7

20°

68°

12.5

25°

77°

10.0

30°

86°

8.1

35°

95°

6.5

40°

104°

5.3

45°

113°

4.4

50°

122°

3.6

Wiring of the ICM325A to a heat pump is the same as for air conditioning with the 

exception of the Motor 2 output and the reversing valve input. For a heat pump, the 

ICM325A Motor 2 terminal is connected to the outdoor fan relay input power terminal 

(com) on the defrost board. The condenser fan common remains connected to the 

normally closed terminal of the fan relay on the defrost board. Apply the reversing 

valve voltage to the HP RV input in parallel with the existing reversing valve; for cool 

active reversing valves a jumper will have to be placed at the HP O RV jumper posi-

tion. NOTE: Line one of the ICM325A must share the same leg of power that is feed-

ing the common of the run capacitor.

AIR CONDITIONING SYSTEM WIRING

HEAT PUMP SYSTEM WIRING

Connect the wires from the contactor (load side), run capacitor, and the condenser 

fan as shown in diagram above. If control voltage is desired, ensure the jumper is 

placed on the control voltage enable input and the proper voltage (24-240 VAC) is 

applied to the control voltage input. Place the temperature probe at T1/P1 and 5V and 

mount the probe on a U-bend in the upper third of the condenser. If two temperature 

probes are needed, wire the additional temperature probe to T2/P2 & 5V. If a pressure 

transducer is used, mount the transducer on the discharge line at the service fitting. 

Connect the red wire to +5V, the black wire to GND and the BWG (blue/white/green) 

wire to T1/P1 input. If two pressure sensors are used, connect the black and red wires 

of the additional pressure sensor to the same points as previously mentioned and 

connect the BWG (blue/white/green) wire to TP2/P2. NOTE: Line one of the ICM325A 

must share the same leg of power that is feeding the common of the run capacitor.

Pressure (PSIG)

Voltage (VDC)

15

0.5

50

0.8

100

1.2

150

1.6

200

2.0

250

2.4

300

2.8

350

3.2

400

3.6

450

4.0

515

4.5

PRESSURE VS. VOLTAGE

MOTOR 2

ICM325A

LINE 2

LINE 1 / MOTOR 1

120 - 600 VAC

FULL SPEED

VARIABLE SPEED

CONTROL

INPUT

24-240VAC

HP RV

24-240VAC

GND

+5V

T2/P2

T1/P1

CONTROL INPUT
HP

MADE IN THE USA

SENSOR 

ENABLE

 

Line Voltage

120-600 VAC

Place jumper to enable

the control voltage input

24-240 VAC 

Control Voltage 

(optional)

Temperature 

Sensor

O RV

Run

Start

Common

L1

L2

T1

T2

Contactor

Run 

Capacitor

To C

ompr

es

sor

Field

 Ins

tal

led

 W

ire

Com

Herm

Fan

Single 

Phase PSC 

Fan Motor

MOTOR 2

ICM325A

LINE 2

LINE 1 / MOTOR 1

120 - 600 VAC

FULL SPEED

VARIABLE SPEED

CONTROL

INPUT

24-240VAC

HP RV

24-240VAC

GND

+5V

T2/P2

T1/P1

CONTROL INPUT
HP

MADE IN THE USA

SENSOR 

ENABLE

  

Line Voltage

120-600 VAC

Fan 

Relay

Place jumper to enable

the control voltage input Place jumper to 

enable a cool active 

reversing valve at 

the HP O RV input

24-240 VAC 

reversing valve 

input (heat active 

default)

24-240 VAC  

Control Voltage 

(optional)

Temperature 

Sensor

Defrost Board

COMN

Run

Start

Common

C

L1

L2

T1

T2

Contactor

Run 

Capacitor

To C

ompr

es

sor

Field

 Ins

tal

led

 W

ire

Com

Herm

Fan

Single 

Phase PSC 

Fan Motor

O RV

Reviews: