Line voltage:

 120, 208, 240, and 480 VAC

• 

Control voltage:

 18-30 VAC

• 

Frequency:

 50-60 Hz

• 

Operating temperature:

 -40ºF to +176ºF (-40°C to +75°C)

• 

Sensors:

 10K ohms at 77°F (25°C)

• 

Heat pump override:

 24 VAC N.C. or N.O.

 

 

Note:

 A maximum of three sensors can be connected to the control.

• 

Weight:

 12 ounces (341 grams)

 

 

Note:

 

The 

ICM325HN

 should be applied to motors and equipment that have been designated by their 

respective manufacturers as capable of being speed controlled.

•  Mounting:

 

  –  Surface mount using (4) #8 screws
  –  The 

ICM325HN

 should be surface mounted to a clean metal or other thermally conductive surface for 

maximum heat dissipation

  –  It is recommended that the 

ICM325HN

 be mounted away from the condenser exhaust air in order to maintain 

lower operating temperatures

Specifications

Installation of the ICM325HN shall be performed by trained technicians only. Adhere to all local and national 
electric codes. 

Disconnect all power to the system before making any connections.

Caution!

ICM325HN

Installation, Operation & Application Guide

For more information on our complete range of American-made 
products – plus wiring diagrams, troubleshooting tips and more, 
visit us at 

www.icmcontrols.com

Head Pressure 

Control with 

Optional 

Heat Pump Override

Temperature sensitive 

control regulates 

head pressure

1.  Remove power from system.
2.  Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3.  Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal and line 

side to 

Line 2

 terminal.

4.  Make 24 VAC, probe and HP connections.
5.  Verify wiring is correct.
6.  Power up system and check operation.

Connections for ICM325HN at 480 VAC

PSC 

Fan 

Motor

Run 

Capacitor

480 VAC

Typical condenser fan

Line

1

480 VAC

Line

2

Motor

2

PSC 

Fan 

Motor

Run 

Capacitor

480 VAC

Field  

Installed 

Wire

Typical condenser 

fan with ICM325HN 

installed

Connections for ICM325HN at 120/208/240 VAC

1.  Remove power from system.
2.  Field install a wire from 

Line 1

 wire to 

Line 1

 terminal.

3.  Cut 

Line 2

 wire; affix motor side to 

Motor 2

 terminal and line 

side to 

Line 2

 terminal.

4.  Make 24 VAC, probe and HP connections.
5.  Verify wiring is correct.
6.  Power up system and check operation.

PSC 

Fan 

Motor

Run 

Capacitor

Line

1

120/240 

VAC

Line

2

Motor

2

PSC 

Fan 

Motor

Run 

Capacitor

Field  

Installed 

Wire

Typical condenser 

fan with ICM325HN 

installed

120/208/240 

VAC

Typical condenser fan

120/208/240 

VAC

Connecting the Probe

Example

1.  Install the temperature probe several bends into the condenser. It can be attached to the 

U-bend or placed between the fins in the upper 1/3 of the condenser (see other side for 
more information).

 

 

Note:

 

The response of the system can be fine tuned by repositioning the probe. Place 
the probe on the condenser where it is 100°F when pressures are correct for 
best response.

2.  Connect the two wires from the sensor to the terminal  

block where it is marked 

PROBE S1

. If additional probes are necessary for multiple 

refrigerant circuits, they may be attached to terminals marked 

PROBE S2

 and 

PROBE S3

.

 

 

Note:

 

The control will respond to the probe that senses the highest temperature.

Connections for Air Conditioning Only

1. 

For non-heat pump applications

, the heat 

pump select jumper must be in the 

Default

 

(

N.O.

) position, and the HP terminals must 

be left unconnected.

2.  Set the 

Cutout Speed

 and the 

Hard Start 

Time

 to the appropriate positions for the type 

of motor you have (see other side).

Temperature Probe

24 VAC

Additional 

Probes

Probe S1

HP

Heat Pump 
Select Jumper 
Default Position

ICM325HN Typical Installation