background image

ICM491

Single Phase Line Monitor

Reliable line voltage protection for single phase systems

7313 William Barry Blvd., North Syracuse,  NY  13212

(Phone) 

315-233-5266

  (Toll Free) 

800-365-5525

(Fax) 

315-233-5276

www.icmcontrols.com

LII114-1

Protects against High/Low 

voltage and rapid system 

recycling, 95-270 VAC 

operation, adjustable  

anti-short cycle timer...

The 

ICM491

 was specifically designed 

to guard equipment against damage 

caused by under/over voltage conditions 

and/or rapid system recycling.

DESCRIPTION

• 

5-Second Interrogation Delay...

 helps 

prevent nuisance tripping

• 

LED Indication... 

normal run and fault 

indications

• 

95-270 VAC Operation...

 in a single 

model

• 

Integral Anti-Short Cycle 

Protection...

 “Delay on break” circuit 

provides adjustable (.1 to 10 minutes) 

lockout delay to prevent rapid system 

recycling; no external ASC timers 

required

• 

Meets IEEE 587...

 A&B for transient 

protection

FEATURES

Input

• 

Line Voltage:

 95-135 VAC or 190-270 VAC  

 

 

(selectable)

• 

Maximum Operating Input:

 142-275 VAC

• 

Line Frequency:

 50-60 Hz

Output

 

Type:

 Relay, energized upon acceptable  

 

 

conditions

• 

Form:

 SPDT, Single Pole, Double Throw

• 

Ratings:

 6A @ 120 VAC resistive

   

  5A @ 240 VAC resistive

Response Times

• 

Line Dropout:

 .05 seconds (typical)

• 

Line Voltage Sag:

 5 seconds (typical)

• 

Turn On (sec):

 Based on minimum time  

 

 

selected

Lockout Delay Timer

• 

Dry Relay Contacts

 

Time Delay:

 Adjusts from 6-600 seconds 

 

(+/- 10%)

Under Voltage Protection

• 

Voltage Dropout:

 Setpoint is -12%

• 

Voltage Pickup:

 Setpoint is -8%

Over Voltage Protection

• 

Voltage Dropout:

 Se12%

• 

Voltage Pickup:

 Se8%

Environmental

• 

Operating Temperature:

 -40°F to +167°F 

 

(-40°C to +75°C)

• 

Transient Protection:

 Meets IEEE 587 

Standards for Categories A&B without false output 

or degradation 

 

– (6Kv 0.5 µs  x 100 KHz Ring Wave)

 

– (6Kv 1.2 x 50 µs Impulse Wave)

Mechanical

• 

Mounting:

 Surface mount using (2) #8 screws

• 

Terminations:

 .25” male quick-connect  

 

 

terminals

SPECIFICATIONS

Reviews: