LIAF236-1

ICM

550

DEFROST CONTROL

Replaces

•  Grasslin: 010-0011B, DT040, DT140, DTAV40, DTMV, DTSX

•  Paragon: 8041, 8045, 8047, 8141, 8143, 8145, 8245, 8247

•  Precision: 6041, 6045, 6047, 6141, 6145

• ICM550 defrost control module

• Bracket mount

• Installation guide

• Terminal block & wiring diagram label sheet

• #8 x 1/2” sheet metal screws (3)

• #6 x 1/2” hex head screws (4)

Package Contents

ELECTRICAL SHOCK HAZARD! 

Turn off power at the main service panel by removing 

the fuse or switching the appropriate circuit breaker 

to the OFF position before working on a high voltage 

control.

CAUTION!

 

Installation of the ICM550 shall be performed by trained 

technicians only. Adhere to all local and national electric 

codes. 

WARNING!

 

Never turn the dial backward, always turn the dial clockwise 

to adjust. Do not attempt to touch or adjust the hands of the 

clock as this may cause permanent damage to the clock.

> > > CAUTION < < <

Default Wiring Diagram

Specifications

Inputs:

• Nominal voltage range: 120-240 VAC

• Frequency: 60Hz

Outputs:

• Type: Relay

Contact Ratings:

• Compressor: [2]&[4]: 30A R, 1HP@120VAC, 2HP@240VAC

• Electric heat: [1]&[3]: 40A R, 1HP@120VAC, 2HP@240VAC

• Fan: [1]&[F]: 30A R, 1HP@120VAC, 2HP@240VAC

Environmental

• Operating temperature: -40 to +131°F

• Operating humidity: 0-95%, non-condensing

Mechanical

• Construction: Open board (plastic bracket mounted)

• Mounting: Vertical or Horizontal orientation

Timing

•  Minimum defrost time: 15 minutes

•  Maximum defrost time: 23 hours 45 minutes

•  Terminate defrost: Defrost can be terminated by shorting “X to N”
Status LED

•  Defrost mode: (Red LED)

•  Refrigeration mode: (Green LED)

Terminal Block

USE COPPER WIRES ONLY”  
Tightening torque 15 in-lb.

The following example shows the  

clock set to 2:30 PM:
Turn the outer dial clockwise 

until the inner clock hands 

point to the correct time. 

Each tick mark on the outer  

dial represents 15 minutes. 
The inner dial is representative  

of conventional clock, with the  

printed “hand” showing the hour  

and the physical hand showing the  

minute. The time displayed on the inner dial will always 

correspond with the time on the outer dial.

To Set the Current Time

Decide the amount of defrost time  

necessary for your environment  

and the hours which you want  

defrost to occur. Next, set the  

switches for each 15 minute  

interval of defrost you require 

 by moving the switch to the  

outer position. 
Each switch represents a 15  

minute interval of defrost and  

there are 4 intervals per hour.
In this example, the system will begin one defrost cycle at 

the 5:00 PM, which will last for 45 minutes (3 intervals). The 

unit will resume normal operation at 5:45 PM.
If multiple defrost cycles are required, please select the 

appropriate dipswitches to represent each 15 minute interval 

throughout the 24 hour period where defrost is desired.

To Set Defrost Time

F

3

N

X

1

2

4

T-Stat

Fan

 

Defrost

Heater

120

VAC

L1

L2

Defrost 

Thermostat 

w/ Fan Delay

K

1

K

2

Switch Position 

Mode A

Compressor 

Contactor Coil 

Solenoid Valve