Maximum compressor cycles allowed per hour
(-, 2-6)
- = as many as needed, 2-6 = maximum cycles/hour
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
8.
Room temperature offset
(+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note:
When not set to 0,
ROOM
will display
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
7.
Maximum Heat Setpoint
(55°F to 90°F) (13°C to 32°C)
Adjust to control the maximum Heat set temperature allowed.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
6.
Minimum Cool Setpoint
(45°F to 75°F) (7°C to 24.0°C)
Adjust to control the minimum Cool set temperature allowed.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
4.
Temperature Differential – Stage 3 – (1°F to 6°F) (0.5°C to 3.0°C) –
Set the number of degrees between when stage 2 turns on and stage
3 turns on.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
5.
Staged Off Outputs
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = Economy Mode – Outputs are staged on and off in accordance
with set point and differential.
0 = Comfort Mode – Outputs are staged on and and all stages cycle
off simultaneously when set point is satisfied.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE