SimpleSet
TM
Field Programming
This feature is used for transferring the configuration from the master to the target thermostat . All
thermostats for a job can be mounted and powered up . Configure one thermostat . This will be the
master . The master will be used to copy the configuration to the rest of the thermostats .
Preparing the master to Send:
1 . The master must be powered with 24 VAC .
2 . Verify the master thermostat is in
OFF
mode .
3 . Press
SYS
(left) button until
OFF
mode displays .
4 . Remove cover of the master thermostat by gently pulling near one of the corners
at the top of the thermostat .
5 . Press the
up
and
down
buttons and
CONFIG
switch simultaneously for 5 seconds .
6 . The
OUT
screen displays indicating the master thermostat is ready to
transfer data .
Note:
Press the
up
and
down
buttons and
CONFIG
switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF
mode .
7 . Turn off power to the master and remove it from the wall .
8 . Connect the master to the target using the 3 wire connector . Attach one end to
the Master’s FP pins and the other end to the Target’s FP pins .
Note:
Target thermostat must be powered with 24 VAC for field
programming to occur
When the connection has been made correctly, the master thermostat will power up and the target will
count from 5 down to 1 . It will then display the
LOCK
confirming the data has been saved in memory .
When all target thermostats have been completed, reinstall the master thermostat .
Press the
up
and
down
buttons and the
CONFIG
switch simultaneously for 5 seconds to exit from the
data transfer mode and to return the master thermostat to the
OFF
mode .
OFF
FP pins
S1 S2 R
C
W
O/B
G
Y1 W2
W3
Y2
RESET
CONFIG
FP
Requires SimpleSet
TM
Transfer Cable (ACC-WIH21)