background image

Troubleshooting

Symptom

Remedy

No display

Check for 24 VAC at thermostat; display is blank when 24 VAC is not present
Time and day of week must be reset after extended power loss

System fan does not come on properly

Verify wiring is correct, check Gas/Electric Configuration (see Setting 4, Page 12)

All thermostat buttons are inoperative

Verify 24 VAC is present; unit locks out when 24 VAC is not present

No response with first button press

First button press activates backlight only

Program schedule activates at the wrong 

time

Check time (AM/PM) set on thermostat (see Setting the Time, Page 20)

Thermostat turns on and off too frequently

Adjust temperature differential (see Configuration Mode Setting 2, Page 11)

Thermostat does not follow program

Verify it is operating in program mode (PROG displays); check time (AM/PM); check 

if in 2 hour program override

Fan runs continuously

Press FAN (right) button to turn fan off

Fan turns on occasionally

Program Mode: Check programmable fan setting in program schedule  

(see Page 22)

Status indicator light not on during call

Turn status indicator function on (see Configuration Mode Setting 12, Page 15)

Room temperature is not correct

Calibrate thermostat (see Configuration Mode Setting 8, Page 14) 
If remote sensor is used, check S1 and S2 terminal connections

displays when any button is pressed

Thermostat has the button lockout function activated (see Lockout Feature, Page 

23 and Configuration Mode Setting 5, Page 13)

on display instead of room temp .

Check for a bad connection at S1 and S2 terminals, if used (see Configuration 

Mode Setting 10, Page 14)

Heat or Cool not coming on

Verify wiring is correct, verify RC/RH jumper is in place (for single transformer 

system)

Remote or outdoor sensor not accurate

Press SYS and Down buttons simultaneously to display remote or outdoor 

temperature . Verify connections at S1 and S2 terminals .

Problem not listed above

Press Reset button once*

* Reset Button Function

  Time and day are reset, configuration and program settings are unchanged .

Summary of Contents for SC 5011

Page 1: ...visit us at www icmcontrols com 7 Day 5 2 Day or 5 1 1 Day Programmable Configurable Single Stage Heat Cool Systems Single Stage Heat Pump Systems Large Display With Backlight Selectable Fahrenheit or Celsius Compatible with Gas Oil or Electric SimpleSet Field Programming Status Indicator Light Relay Outputs minimum voltage drop in thermostat Remote Sensor Compatible Ideally Suited for Residential...

Page 2: ... Thermostat 4 Wiring Diagrams 5 Remote or Outdoor Sensor Installation Optional 9 Configuration Mode 10 Configuration Mode Settings 11 Mode of Operation 16 Operating Modes 17 Testing the Thermostat 19 Setting the Time and Day of the Week 20 Programming 21 Lockout Feature 23 Factory Preprogramming 24 Personal Program Schedule 24 SimpleSetTM Field Programming 26 Troubleshooting 27 ...

Page 3: ... S1 S2 Y W O B G RC RH C RESET CONFIG RC RH Parts Diagram Configuration switch Reset switch Left system button Right fan button Down button Up button Field programming pins RC RH Jumper FP ...

Page 4: ...ffset activated Electrical rating 24 VAC 18 30 VAC 1 amp maximum per terminal 3 amp maximum total load Temperature control range 45 F to 90 F 7 C to 32 C Accuracy 1 F 0 5 C System configurations 1 stage heat 1 stage cool heat pump gas oil electric Timing Anti short Cycle 4 minutes Backlight Operation Terminations S1 S2 Y W O B G RC RH C ...

Page 5: ...nd building codes Do not use air conditioning when the outdoor temperature is below 50 degrees this can damage your A C system and cause personal injuries Use this thermostat only as described in this manual To Remove Existing Thermostat ELECTRICAL SHOCK HAZARD Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position before remo...

Page 6: ... of the thermostat 4 Mark the placement of the mounting holes 5 Set thermostat base and cover away from working area 6 Using a 3 16 drill bit drill holes in the places you have marked for mounting 7 Use a hammer to tap supplied anchors in mounting holes 8 Align thermostat base with mounting holes and feed the control wires through slit in thermal intrusion barrier and into wire opening 9 Use suppl...

Page 7: ... Hardwired 3 Wire Single Transformer Hardwired 4 Wire Single Transformer Wiring Diagrams ...

Page 8: ... Hardwired 5 Wire Two Transformer Both transformers must be in phase Hardwired 4 or 5 Wire Single Transformer Fan Control IMPORTANT Before wiring remove pre installed RC RH jumper ...

Page 9: ... Hardwired Cool or Heat Active Reversing Valve ...

Page 10: ... Hardwired 4 Wire Single Transformer ...

Page 11: ...ould run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor Connect the shielding of the wire to the S2 terminal on the thermostat 5 Configure the thermostat to operate with the remote sensor see Configuration Mode setting 10 Page 14 Note Remote or outdoor sensor rea...

Page 12: ...ONFIG switch for 1 second Press the up or down button to change settings within each screen Down button Up button Press the right button to advance to the next screen Note Pressing the left button will return you to the previous screen Left button Right button The configuration mode is used to set the SC5011 to match your heating cooling system The SC5011 functions with heat pump air conditioning ...

Page 13: ...dband value Press the right button to advance to the next screen 2 Temperature Differential 1 F to 5 F 0 5 C to 2 5 C Set the number of degrees between your setpoint temperature and your turn on temperature Press the up or down button to set differential value Press the right button to advance to the next screen 1 Temperature Scale F or C Choose Fahrenheit or Celsius Press the up or down button to...

Page 14: ... the next screen 4 System Set for heat pump non heat pump reversing valve operation and number of compressors in your system Choose System Reversing Valve Active Number of Compressors or Compressor Stages Type of Heat Heat Pump HP O 1 HP b 1 Non Heat Pump Heat Gas Heat Electric ...

Page 15: ...de cannot be changed when the thermostat is locked Press the up or down button to select Press the right button to advance to the next screen 6 Maximum Heat Setpoint 45 F to 90 F 7 C to 32 C Adjust to control the maximum heat set temperature allowed Press the up or down button to select Press the right button to advance to the next screen 7 Minimum Cool Setpoint 45 F to 90 F 7 C to 32 C Adjust to ...

Page 16: ...ton to select Press the right button to advance to the next screen 9 Maximum Cycles Allowed Per Hour 2 6 as many as needed 2 6 maximum cycles hour Press the up or down button to select Press the right button to advance to the next screen 8 Room Temperature Offset 9 F to 9 F 4 5 C to 4 5 C Adjust to calibrate displayed room temperature to match actual room temperature Note When not set to 0 will di...

Page 17: ...th first stage Press the up or down button to select Press the CONFIG button for 2 seconds to exit configuration OFF 11 Cooling Fan Delay Off Time 0 30 60 90 seconds Select the fan purge time for cooling Press the up or down button to select Press the right button to advance to the next screen ...

Page 18: ...es after it turns off This protects your compressor The SC5011 has five possible operating modes OFF Heat Cool Heat Cool and Program mode In off mode the thermostat will not turn on heating or cooling devices The manual fan can be turned on in all operating modes using the fan button In heat mode the thermostat controls the heating system In the cool mode the thermostat controls the cooling system...

Page 19: ...erating mode by pressing the FAN right button The word FAN shows on the display and the fan icon appears when the fan operates Heat Mode In this mode the thermostat controls the heating system When the heat outputs the flame icon apprears on the display Note For heat pumps there is a four minute delay for your compressor to restart after it has turned off Cool Mode In this mode the thermostat cont...

Page 20: ...e cool and heat mode Program Mode In this mode the program function is on PROG displays and the thermostat will automatically be controlled by the set program schedule Program mode can function with heat mode cool mode or heat cool mode The program schedule can be overridden by changing the set temperature up or down button After 2 hours the program schedule will automatically be resumed To manual...

Page 21: ... set temperature 2 degrees below the room temperature and the heat should turn off There may be a fan delay on your system Note For heat pumps there is a four minute delay to protect your compressor after it turns off To bypass the compressor time delay go to OFF mode for 5 seconds PM Cool Test 1 Press SYS left button until cool mode is displayed 2 Adjust set temperature so it is 5 degrees below r...

Page 22: ...nds to lock values into memory and return to the OFF mode or press the FAN right button once to enter programming 4 Press the FAN right button once to select minutes minutes flashing Press the up or down button to adjust the minutes 3 Time displays hour flashing Press the up or down button to adjust the hour 2 Press and hold the PROG button SYS left and FAN right buttons pressed simultaneously in ...

Page 23: ...options Note The days of the week shown on the display will be programmed simultaneously The screens are listed below Screen 1 SUN MON TUE WED THU FRI SAT Screen 2 MON TUE WED THU FRI Screen 3 MON Screen 4 TUE Screen 5 WED Screen 6 THU Screen 7 FRI Screen 8 SUN SAT Screen 9 SAT Screen 10 SUN Program Overview The SC5011 programmable thermostat has four periods MORN DAY EVE NITE that are customizabl...

Page 24: ... different minutes Press FAN right button to advance to the next screen Heat set temperature displays Use the up or down button to adjust the heat set temperature Press FAN right button to advance to the next screen Cool set temperature displays Use the up or down button to adjust the cool set temperature Press FAN right button to advance to the next screen Programmable fan screen displays Use the...

Page 25: ...ment is limited Select the appropriate lockout from Configuration Mode Settings Step 5 Page 13 of this guide To activate the LOCK feature 1 Simultaneously press the SYS FAN and UP buttons for 10 seconds 2 will display and the lockout function will be enabled To deactivate the LOCK feature repeat steps 1 and 2 above ...

Page 26: ...AT 70 F HEAT 62 F HEAT 70 F HEAT 62 F COOL 78 F COOL 85 F COOL 78 F COOL 82 F FAN Off FAN Off FAN Off FAN Off MONDAY thru SUNDAY Personal Program Schedule MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN MONDAY 1 TUESDAY 2 MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN WEDNESDAY 3 MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN ...

Page 27: ...Y EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL FAN FAN FAN FAN ...

Page 28: ...Press the up and down buttons and CONFIG switch simultaneously for 5 seconds to exit from data transfer mode and to return the master to the OFF mode 7 Turn off power to the master and remove it from the wall 8 Connect the master to the target using the 3 wire connector Attach one end to the Master s FP pins and the other end to the Target s FP pins Note Target thermostat must be powered with 24 V...

Page 29: ... turn fan off Fan turns on occasionally Program Mode Check programmable fan setting in program schedule see Page 22 Status indicator light not on during call Turn status indicator function on see Configuration Mode Setting 12 Page 15 Room temperature is not correct Calibrate thermostat see Configuration Mode Setting 8 Page 14 If remote sensor is used check S1 and S2 terminal connections displays w...

Page 30: ...This page left blank intentionally ...

Page 31: ...This page left blank intentionally ...

Page 32: ...anty the Buyer shall 1 Notify the Seller promptly of any claim submitting date code information or any other pertinent data as requested by the Seller 2 Permit the Seller to inspect and test the product claimed to be defective Items claimed to be defective and are determined by Seller to be non defective are subject to a 30 00 per hour inspection fee This warranty constitutes the Seller s sole lia...

Reviews: