SC1001/SC1001V Wiring Diagrams

Heating Only

3-Wire, Single Transformer

4-Wire, Single Transformer

Fan

Control

Heating and Cooling

5-Wire, Single Transformer

Fan

Control

Cooling Only

4-Wire 

Single Transformer

R

C

Y

G

W

B

O

2

4 VAC

120 VAC

HOT

Transformer

Cooling

Control

Fan

Control

Operation

A Quick Test

 

CAUTION!

Do not switch system to cool if the temperature is below 50°F. This can 

damage the air conditioning system and may cause personal injury.

Do not short jumper across terminals on the gas valve or at the system control to test 
installation.  
Action:

  Set the 

Cool/Off/Heat

 switch to 

Cool

.  Slide the temperature bar down to lowest setting 

(45°F). 

 

Result:

 

The A/C system and fan should turn on.

Action:

  Set the 

Cool/Off/Heat

 switch to 

Off

 

Result:

 The A/C should turn off (There may be a fan delay).

Action:

  Set the 

Cool/Off/Heat

 switch to 

Heat

.  Slide the temperature bar up to highest setting (90°F). 

 

Result:

 The heating system and fan should turn on (There may be a time delay depending 

on your system).

Action:

  Set the 

Cool/Off/Heat

 switch to 

Off

 

Result:

  The heating system should turn off (There may be a fan delay).

Action:

  Set the 

Fan Auto/On

 switch 

On

.

 

 

Result:

 The blower fan should turn on.

Action:

  Set the 

Fan Auto/On

 switch to 

Auto

.  

 

Result:

 

The blower fan should turn off.

If the above test was successful, you have a proper installation. Be sure to return your thermostat bar 
to your desired setting.

If not:

 

Double check that wires are securely connected and are connected to the proper terminals. 
Consult the troubleshooting section.

ONE-YEAR LIMITED WARRANTY

The Seller warrants its products against defects in material or workmanship for a period of one (1) year 
from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue 
a non-case credit for the purchase prices of the goods which are provided to be defective. The warranty 
and remedies set forth herein do not apply to any goods or parts thereof which have been subjected to 
misuse including any use or application in violation of the Seller’s instructions, neglect, tampering, improper 
storage, incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly 
administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code 
information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test 
the product claimed to be defective. Items claimed to be defective and are determined by Seller to be non-
defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller’s sole liability 
hereunder and is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated 
in writing, Seller makes no warranty that the goods depicted or described herein are fit for any particular 
purpose.

LIAF002

Patent No. 424,953

7313 William Barry Blvd., North Syracuse,  NY  13212

(

Toll Free

) 800-365-5525     (

Phone

) 315-233-5266     (

Fax

) 315-233-5276

www.icmcontrols.com

Heat Pump

Heat Active 

Reversing Valve

Cool Active 

Reversing Valve

R

C

Y

G

W

B

O

R

C

Y

G

W

B

O

2

4 VAC

120 VAC

HOT

Transformer

2

4 VAC

120 VAC

HOT

Transformer

Compressor 

Contactor

Reversing 

Valve

Compressor 

Contactor

Reversing 

Valve

Place jumper between “W” and “Y” terminals.

Fan

Control

Fan

Control

Setting the Room Temperature (Setpoint Temperature)
Step 1:

  Slide the temperature bar to your desired setting.

Step 2:

  Move the 

Fan Auto/On

 switch into the 

Auto

 position.

Step 3:

  Move the 

Cool/Off/Heat

 switch to 

Cool

 or 

Heat

, depending on the season.

Troubleshooting

Symptom

Remedy

The system isn’t turning on

Check the wiring diagrams
Verify 24 VAC is at thermostat

Thermostat is not properly controlling 

the fan

Check that the 

Gas/Electric

 jumper setting matches your 

system (gas or electric)

Temperature setting does not appear 
accurate

Verify no heat producing objects are located near the 

thermostat

Verify thermostat has adequate air flow to it