Symptom
Remedy
No display
Check for 24 VAC at thermostat; display is blank when 24 VAC is not present or if
batteries are completely discharged. Time and day of week must be reset after extended
power loss.
System fan does not come on properly
Verify wiring is correct, check Gas/Electric Configuration (see Setting 4).
No response with first button press
First button press activates backlight only (when back light is configured “ON”).
Program schedule activates at the wrong
time
Check time (AM/PM) set on thermostat (see Setting the Time).
Thermostat turns on and off too frequently
Adjust temperature differential (see Configuration Mode Setting 2).
Thermostat does not follow program
Verify it is operating in program mode (PROG displays); check time (AM/PM); may be in
2 hour program override.
Fan runs continuously
Press FAN (right) button to turn fan off.
Fan turns on occasionally
Program Mode: Check programmable fan setting in program mode schedule.
Status indicator light not on during call
Turn status indicator function on (see Configuration Mode Setting 12).
Room temperature is not correct
Calibrate thermostat (see Configuration Mode Setting 8). If remote sensor is used, check
S1 & S2 terminal connections. Press
SYS
and
down
buttons to display outdoor
temperature.
displays when any button is pressed
Thermostat has the button lockout function activated (see Lockout Feature, and
Configuration Mode Setting 5).
on display instead of room temp.
Check for a bad connection at S1 & S2 terminals, if used (see Configuration Mode
Setting 10).
Heat or Cool not coming on
Verify wiring is correct, verify RC/RH jumper is in place (for single transformer system).
Remote or outdoor sensor not accurate
Press
SYS
and
down
buttons simultaneously to display remote or outdoor temperature.
Verify connections at S1 and S2 terminals.
LO BAT
on display
Replace batteries with two fresh “AAA” batteries.
LO BAT
may display if no batteries are
installed and there is a loss of power.
Problem not listed above
Press Reset button once*.
* Reset Button Function
:
Time and day are reset, configuration and program settings are unchanged.
Troubleshooting
Program Overview
The
SC5010
programmable thermostat has four periods (MORN, DAY, EVE, NITE) that are customizable for each
day of the week. Each period will have a start time, heat temperature, cool temperature and programmable fan
option. The
SC5010
monitors the day and time, while maintaining the specific conditions you have chosen for each
period in your program.
Mode of Operation
The
SC5010
is a programmable, manual or auto changeover, single stage heat, single stage cool thermostat. It
functions with air conditioning, heat pumps, gas, oil or electric heat systems.
The thermostat activates the heating appliance when the room temperature is below the set heat temperature
(by the differential temperature) and the red indicator light (configurable) on the thermostat will light. The
SC5010
will stop outputting and the red light will turn off when the call for heat has been satisfied. With heat pumps, the
thermostat will not let the compressor come on for 4 minutes after it turns off. This protects your compressor.
When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling
device is activated and the green indicator light (configurable) on the thermostat will turn on. The
SC5010
will
stop outputting and the green light will turn off when the call for cooling is satisfied. The thermostat will not let the
compressor come on for 4 minutes after it turns off. This protects your compressor.
The
SC5010
has five possible operating modes:
OFF
,
Heat
,
Cool
,
Heat & Cool
, and
Program
mode. In off mode,
the thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all operating modes
using the fan button. In heat mode, the thermostat controls the heating system. In the cool mode, the thermostat
controls the cooling system. In heat & cool mode, the thermostat controls both the heating and cooling systems. In
program mode, the thermostat will automatically be controlled by the set program. Program mode can function with
heat mode, cool mode, or heat & cool mode. The clock display alternates with the set temperature display for heat &
cool mode.
The programmable fan feature can be used to run the fan during occupied periods.
The program schedule can be overridden by changing the set temperature (up or down button). This puts the
SC5010
thermostat into a 2-hour temporary hold. After 2 hours, it will automatically return to the program schedule.
The
SC5010
also has a button lockout feature. This enables the thermostat to be set to the proper mode and
temperature and locked so it cannot be tampered with.
12.
Status Indicator Light
(0 or 1)
0 = Status indicator never on (best for long battery life)
1 = Status indicator on with first stage
Press the
up
or
down
button to select.
Press the
right
button to advance to the next screen.
13.
Back Light
(0 or 1)
0 = Back light never on (best for long battery life)
1 = Back light on when button pressed
Press the
up
or
down
button to select.
Press the
CONFIG
button for 2 seconds to exit configuration.
From any of the previous screens, you can press the
FAN
(right) button to begin entering your program schedule.
The days shown on the display will all be programmed simultaneously.
Once the
FAN
(right) button is pressed,
MORN
blinks.
Use the
up
or
down
button to select a different period (
MORN
,
DAY
,
EVE
,
NITE
).
Press
FAN
(right) button to advance to the next screen. Transition time
hour
blinks.
Use the
up
or
down
button to select a different hour.
Press
FAN
(right) button to advance to the next screen. Transition time
minutes
blink.
Use the
up
or
down
button to select different minutes.
Press
FAN
(right) button to advance to the next screen.
Heat set temperature
displays.
Use the
up
or
down
button to adjust the heat set temperature.
Press
FAN
(right) button to advance to the next screen.
Cool set temperature
displays.
Use the
up
or
down
button to adjust the cool set temperature.
Press
FAN
(right) button to advance to the next screen.
Programmable fan
screen displays.
Choose:
OFF
– Programmable fan disabled.
ON
– Indoor fan on continuously during the period.
Repeat above steps to program the four periods per day.
When the program schedule is complete, press and hold the
PROG
button (
SYS
and
FAN
buttons pressed
simultaneously) in for 2 seconds to return to the
OFF
mode.
Programming
From this screen you have 2 options:
1. Press the
FAN
(right) button to begin programming all 7 days at one time, or
2. Press the up button to see the other programming options.
Note:
The days of the week shown on the display will be programmed simultaneously.
The screens are listed below.
SUN MON TUE WED THU FRI SAT
PROG
Screen 1
SUN
MON
TUE
WED
THU
FRI
SAT
Screen 2
MON
TUE
WED
THU
FRI
Screen 3
MON
Screen 4
TUE
Screen 5
WED
Screen 6
THU
Screen 7
FRI
Screen 8
SUN
SAT
Screen 9
SAT
Screen 10
SUN
Setting the program schedule:
1. Press the
SYS
(left) button until you are in
OFF
mode.
2. Press and hold the
PROG
button (
SYS
and
FAN
buttons pressed simultaneously) for 6 seconds.
3. Press the
FAN
(right) button 3 times.
4. SUN thru SAT are blinking.
Setting the Time and Day of the Week
TODAY
MON
5. Press the
FAN
(right) button once to select day of the week (TODAY flashing).
Press the
up
or
down
button to select current day of the week.
Note:
At any time, press the
SYS
(left) button to return to the previous screen or
press the
FAN
(right) button to advance to the next screen.
Press the
PROG
button in for 2 seconds to lock values into memory and return to the
OFF mode or press the
FAN
(right) button once to enter programming.
3. Time displays (hour flashing).
Press the
up
or
down
button to adjust the hour.
2. Press and hold the
PROG
button (
SYS
(left) and
FAN
(right) buttons pressed
simultaneously) in for 6 seconds.
1. Press the
SYS
(left) button until you are in the OFF mode.
The time and day of the week must be set for your program schedule to operate correctly.
4. Press the
FAN
(right) button once to select minutes (minutes flashing).
Press the
up
or
down
button to adjust the minutes.
Operating Modes
There are five possible operating modes for the
SC5010
. Off, Cool, Heat, and Cool & Heat modes are accessed
by pressing the
SYS
(left) button. Program mode is accessed by pressing the
SYS
(left) and
FAN
(right) buttons
simultaneously.
OFF Mode
• In this mode, the thermostat will not turn on the heating or cooling
devices
Note:
The indoor fan can be turned on manually in every operating mode by
pressing the
FAN
(right) button. The word
FAN
shows on the display and
the fan icon appears when the fan operates.
OFF
Testing the Thermostat
Once the thermostat is configured, it should be thoroughly tested.
CAUTION!
:
Do not energize the air conditioning system when the outdoor temperature is below 50
degrees. It can result in equipment damage or personal injury.
Heat Test
1. Press
SYS
(left) button until heat mode is displayed.
2. Adjust the set temperature so it is 5 degrees above the room temperature.
3. Heat should come on within a few seconds. Red LED may turn on.
4. Adjust the set temperature 2 degrees below the room temperature and the heat
should turn off. There may be a fan delay on your system.
Note:
For heat pumps, there is a four-minute delay to protect your compressor after it turns off.
To bypass the compressor time delay, go to
OFF
mode for 5 seconds.
PM
Cool Test
1. Press SYS (left) button until cool mode is displayed.
2. Adjust set temperature so it is 5 degrees below room temperature.
3. A/C should come on within a few seconds. Green LED may turn ON.
4. Adjust the set temperature 2 degrees above the room temperature
and the A/C should turn off. There may be a fan delay on your system.
Note:
There is a four-minute time delay to protect the compressor after it turns off.
To bypass the compressor time delay, go to
OFF
mode for 5 seconds
PM
Fan Test
1. Press
FAN
(right) button. Fan displays. Indoor fan turns ON.
2. Press
FAN
(right) button. Indoor fan turns OFF.
PM
OFF
Heat Mode
• In this mode, the thermostat controls the heating system. When the heat outputs,
the flame icon apprears on the display.
Note:
For heat pumps, there is a four minute delay for your compressor to
restart after it has turned off.
Cool Mode
• In this mode, the thermostat controls the cooling system. When the cooling outputs,
the snowflake icon apprears on the display.
Note:
There is a four minute delay for your compressor to restart after it has
turned off.
Cool and Heat Mode
(Auto Changeover)
• In this mode, the thermostat controls the cooling and heating systems, automatically
changing over from one to the other as needed.
• The timing display alternates with the set temperature every 10 seconds in the cool
and heat mode.
Program Mode
• In this mode, the program function is on (PROG displays), and the thermostat will automatically be controlled by
the set program schedule. Program mode can function with heat mode, cool mode, or heat & cool mode. The
program schedule can be overridden by changing the set temperature (up or down button). After 2 hours, the
program schedule will automatically be resumed. To manually return to the program schedule, press the PROG
button twice.
PROG
PROG
PROG
SimpleSet
TM
Field Programming
This feature is used for transferring configuration and program schedule from the master to the target thermostat.
All thermostats for a job can be mounted and powered up. Configure and program one thermostat. This will be the
master. The master will be used to copy the program to the rest of the thermostats.
Preparing the master to Send:
1. The master must be powered with 24 VAC.
2. Verify the master thermostat is in
OFF
mode.
3. Press
SYS
(left) button until
OFF
mode displays.
4. Remove cover of the master thermostat by gently pulling near one of the corners at the
top of the thermostat.
Note:
Do not force open. Use a small coin or slotted screwdriver to release tabs if
necessary.
5. Press the
up
and
down
buttons and
CONFIG
switch simultaneously for 5 seconds.
6. The
OUT
screen displays indicating the master thermostat is ready to
transfer data.
Note:
Press the
up
and
down
buttons and
CONFIG
switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF
mode.
7. Turn off power to the master and remove it from the wall.
8. Connect the master to the target using the 3 wire connector. Attach one end to the
Master’s FP pins and the other end to the Target’s FP pins.
Note:
Target thermostat must be powered with 24 VAC for field programming to occur
When the connection has been made correctly, the master thermostat will power
up and the target will count from 5 down to 1. It will then display the
LOCK
confirming the data
has been saved in memory.
When all target thermostats have been completed, reinstall the master thermostat.
Press the
up
and
down
buttons and the
CONFIG
switch simultaneously for 5 seconds to exit from the data transfer
mode and to return the master thermostat to the
OFF
mode.
OFF
Requires SimpleSet
TM
Transfer Cable (ACC-WIH21)
FP pins
Factory Preprogramming
MORN
6:00 AM
DAY
8:00 AM
EVE
6:00 PM
NITE
10:00 PM
HEAT
70°F
HEAT
62°F
HEAT
70°F
HEAT
62°F
COOL
78°F
COOL
85°F
COOL
78°F
COOL
82°F
FAN
Off
FAN
Off
FAN
Off
FAN
Off
MONDAY
thru
SUNDAY
The
SC5010
comes preprogrammed with the following schedule:
THURSDAY
4
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
FRIDAY
5
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
SATURDAY
6
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
SUNDAY
7
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
Personal Program Schedule
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
MONDAY
1
TUESDAY
2
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
WEDNESDAY
3
MORN
DAY
EVE
NITE
HEAT
HEAT
HEAT
HEAT
COOL
COOL
COOL
COOL
FAN
FAN
FAN
FAN
Use the following personal program schedule to record your settings:
Lockout Feature
The
SC5010
has a button lockout feature so the mode cannot be changed and the
temperature adjustment is limited. Select the appropriate lockout from Configuration
Mode Settings (Step 5) of this guide.
To activate the LOCK feature:
1. Simultaneously press the
SYS
,
FAN
and
UP
buttons for 10 seconds.
2. will display and the lockout function will be enabled.
To deactivate the LOCK feature, repeat steps 1 and 2 above.
LIAF060
Patent No. 424,953
7313 William Barry Blvd., North Syracuse, NY 13212
(
Toll Free
) 800-365-5525 (
Phone
) 315-233-5266 (
Fax
) 315-233-5276
www.icmcontrols.com
FIVE-YEAR LIMITED WARRANTY
The Seller warrants its products against defects in material or workmanship for a period of five (5) years from the
date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for
the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein
do not apply to any goods or parts thereof which have been subjected to misuse including any use or application
in violation of the Seller’s instructions, neglect, tampering, improper storage, incorrect installation or servicing not
performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify
the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the
Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective
and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This warranty
constitutes the Seller’s sole liability hereunder and is in lieu of any other warranty expressed, implied or statutory.
Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or described herein are fit for
any particular purpose.