16

 

 

        

 

   

iCON iProtect Instruction Manual Rev 4.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17. Communication link – RS485

 

 

The control panel has a communication interface. The wire communication distance is less than 
1200 metres.  

For those installations or environments which require a longer distance communication, users can 
use RS485 extender, wireless communication or GSM units.  

Please contact White International for more information. 

 

Technical data 

Physical interface 

RS485 Bus Interface: asynchronous semi duplex 

Data format 

1 start bit, 8 data bit, 1 stop bit, no verify 
1 start bit, 8 data bit, 2 stop bit, no verify 
Default: 1 start bit, 8 data bit, 1 stop bit, no verify 

Baud rate 

1200,2400,4800,9600 bps (default 9600bps) 

Communication address 

Setting range of controller address: 1-126 
127: broadcast address, host computer broadcasting, 
slave machine response forbidden 

Protocol type 

MODBUS protocol (RTU) 

Rated input voltage for SC 

AC 240V/50Hz, single phase 

  Installation data 

Wire communication distance  1200 metres max by shield twisted pair cable (STP) 

for RS485 & CAN 
5000 metres max by STP and RS485 extender 

STP 

STP-120U one pair 20AWG for RS485 & CAN 

RS485 extender 

5000 metres (9600bps) 

 

 

Function 

switch 

Capacitor 

terminals 

Capacitor 

connection 

prewired 

NEVER

 

connect 240V 

to terminals  

N1, N2, C  

or  

# 1 - #12 

Summary of Contents for 802697

Page 1: ...iCON iPROTECT Instruction Manual Rev 4 4 1 Auto Restart Pump Controller BIA iPROTECT Single Phase Pump Control and Protection module PN 802697 Installation and Operation Manual...

Page 2: ...where there is the need to control and protect single pump installations managing the automatic operation by a variety of switching methods 2 Contents 1 Introduction 2 2 Contents 2 3 Technical Specif...

Page 3: ...ed input voltage default Trip response times User adjustable Dry run Under load 6 sec Overload 5 sec Under Voltage Less than 5 sec Over voltage Less than 5 sec Recovery times Dry run Under load 30 min...

Page 4: ...by floats or probes Control by pressure switch Control by floats or probes Control by level transducer Control by pressure transducer Control by level transducer Function switch located upper right h...

Page 5: ...4 4 5 6 Operation and Programming navigation In situations where it isn t possible to run the pump to achieve a real world calibration enter the P1 kW rating manually at Parameter 008 See Pg 17 for ad...

Page 6: ...e 0 4 04 9600 bps Default 4 9600 bps Odd Even parity 00 no parity 01 odd parity 02 even parity Default setting 00 no parity Dry run protection trip response time in seconds S Range 0 seconds 60 second...

Page 7: ...is 200 A pump stalled event is a critical error and has no auto restart time The trip voltage of the Under Voltage Protection V Range 0 192V Default setting is 176V The trip voltage of the Over Voltag...

Page 8: ...or to changes to parameters 001 to 017 Changes without consulting White International may void your pump warranty 8 Programming for Cutter Grinder Macerating pumps Pumps fitted with a cutting grinding...

Page 9: ...d be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate the controller before opening the cover to access the low voltage circuit connections W...

Page 10: ...ol terminals 4 5 and 6 must be bridged AND the dry run parameter 009 set to 0 With the dry run parameter inactive the controller still provides protection against overload locked rotor under voltage a...

Page 11: ...onted enclosure is suggested Any electrical alterations or additional connections should be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate...

Page 12: ...he pump will start Destination liquid is above the high level setting The controller will turn the pump off The iProtect has a reliable automatic stop function against pump dry run When used with pump...

Page 13: ...tions or additional connections should be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate the controller before opening the cover to access...

Page 14: ...n OFF The user can exploit this knowledge to control the pump with an external device such as a timer or connection to an irrigation control unit A relay may be necessary Never connect 240V supply to...

Page 15: ...iCON iPROTECT Instruction Manual Rev 4 4 15 16 Bore Pumps Connecting 2 wire and 3 wire bore pumps...

Page 16: ...start bit 8 data bit 2 stop bit no verify Default 1 start bit 8 data bit 1 stop bit no verify Baud rate 1200 2400 4800 9600 bps default 9600bps Communication address Setting range of controller addre...

Page 17: ...its calibration The most reliable means of ensuring the unit is reading a stabilized power supply and that manually programmed parameters are saved correctly is to follow this procedure Reset iProtect...

Page 18: ...ning amps Pump Stalled protection is especially important for pumps with cutting or macerating mechanisms Cut off power supply inspect repair or replace pump Flashing Parameter 011 Voltage is lower th...

Page 19: ...and Consumer Act 2010 Cth for goods purchased in Australia and the Consumer Guarantees Act 1993 NZ for goods purchased in New Zealand 4 Our goods come with guarantees that cannot be excluded under th...

Page 20: ...s or changes in product specifications 2020 Copyright White International Pty Ltd TM WARNING Please be aware that various brands products depicted within this document are subject to trademark patent...

Reviews: