iCON iPROTECT Instruction Manual Rev 4.4

 

 

 

 

 

 

 

Rated power output

 to the pump (P1 power) 

 

                                            Range 0 – 2.99kW 
                                            Default setting is 3.00kW 

          Button Press calibration saves the running value to this location 

 

 

 

 

The trip response ratio of the

 dry-running (underload) 

protection

 as a percentage of the rated current 

 

                                            Range 0 – 95% 
                                            Default setting is 70% 

Control by means of a float attached directly to the pump: set to 

0% 

.

 

 

 

The trip response ratio of the 

Overload Protection

 as a 

percentage of the rated current. 

 

                                            Range 0 – 135% 
                                            Default setting is 135% 

 
 

 

 

The trip response ratio of the 

Pump-Stalled Protection

 as a 

percentage of the rated current. 

 

                                            Range 0 – 240% 
                                            Default setting is 200% 

A pump-stalled event is a ‘critical error’ and has no auto-restart time 

  

 

 

The trip voltage of the 

Under Voltage Protection

 (V) 

 
                                            Range 0 – 192V 
                                            Default setting is 176V 

 

 

 

 

 

The trip voltage of the 

Over Voltage Protection

 (V) 

 
                                            Range 0 – 276V 
                                            Default setting is 253V 

 
 

 

 

 

Note: Only Applicable to Drainage Mode  

Anti-seize parameter.

 

 

 

In auto mode, if pump has not run for XX hours, controller will run the 
pump for 3 seconds. 

                                            Range 0 – 254 hours 
                                            Default setting is 240 hours. 

  

 

 

LCD Button operation lock function 

 

00 = LCD and button function inactive 
01 = LCD and button function activated   

Default setting is 00 = inactive

 

    

If this function is activated, to unlock the controller hold MODE button then 
press and hold the STORE/SET button. The controller will count down 6 – 10 

seconds. Release all buttons and the controller will switch to manual mode 
with all buttons unlocked

 

Summary of Contents for 802697

Page 1: ...iCON iPROTECT Instruction Manual Rev 4 4 1 Auto Restart Pump Controller BIA iPROTECT Single Phase Pump Control and Protection module PN 802697 Installation and Operation Manual...

Page 2: ...where there is the need to control and protect single pump installations managing the automatic operation by a variety of switching methods 2 Contents 1 Introduction 2 2 Contents 2 3 Technical Specif...

Page 3: ...ed input voltage default Trip response times User adjustable Dry run Under load 6 sec Overload 5 sec Under Voltage Less than 5 sec Over voltage Less than 5 sec Recovery times Dry run Under load 30 min...

Page 4: ...by floats or probes Control by pressure switch Control by floats or probes Control by level transducer Control by pressure transducer Control by level transducer Function switch located upper right h...

Page 5: ...4 4 5 6 Operation and Programming navigation In situations where it isn t possible to run the pump to achieve a real world calibration enter the P1 kW rating manually at Parameter 008 See Pg 17 for ad...

Page 6: ...e 0 4 04 9600 bps Default 4 9600 bps Odd Even parity 00 no parity 01 odd parity 02 even parity Default setting 00 no parity Dry run protection trip response time in seconds S Range 0 seconds 60 second...

Page 7: ...is 200 A pump stalled event is a critical error and has no auto restart time The trip voltage of the Under Voltage Protection V Range 0 192V Default setting is 176V The trip voltage of the Over Voltag...

Page 8: ...or to changes to parameters 001 to 017 Changes without consulting White International may void your pump warranty 8 Programming for Cutter Grinder Macerating pumps Pumps fitted with a cutting grinding...

Page 9: ...d be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate the controller before opening the cover to access the low voltage circuit connections W...

Page 10: ...ol terminals 4 5 and 6 must be bridged AND the dry run parameter 009 set to 0 With the dry run parameter inactive the controller still provides protection against overload locked rotor under voltage a...

Page 11: ...onted enclosure is suggested Any electrical alterations or additional connections should be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate...

Page 12: ...he pump will start Destination liquid is above the high level setting The controller will turn the pump off The iProtect has a reliable automatic stop function against pump dry run When used with pump...

Page 13: ...tions or additional connections should be carried out by a suitably qualified technician Ensure suitably rated circuit breakers are installed Isolate the controller before opening the cover to access...

Page 14: ...n OFF The user can exploit this knowledge to control the pump with an external device such as a timer or connection to an irrigation control unit A relay may be necessary Never connect 240V supply to...

Page 15: ...iCON iPROTECT Instruction Manual Rev 4 4 15 16 Bore Pumps Connecting 2 wire and 3 wire bore pumps...

Page 16: ...start bit 8 data bit 2 stop bit no verify Default 1 start bit 8 data bit 1 stop bit no verify Baud rate 1200 2400 4800 9600 bps default 9600bps Communication address Setting range of controller addre...

Page 17: ...its calibration The most reliable means of ensuring the unit is reading a stabilized power supply and that manually programmed parameters are saved correctly is to follow this procedure Reset iProtect...

Page 18: ...ning amps Pump Stalled protection is especially important for pumps with cutting or macerating mechanisms Cut off power supply inspect repair or replace pump Flashing Parameter 011 Voltage is lower th...

Page 19: ...and Consumer Act 2010 Cth for goods purchased in Australia and the Consumer Guarantees Act 1993 NZ for goods purchased in New Zealand 4 Our goods come with guarantees that cannot be excluded under th...

Page 20: ...s or changes in product specifications 2020 Copyright White International Pty Ltd TM WARNING Please be aware that various brands products depicted within this document are subject to trademark patent...

Reviews: