background image

L

O

C

K

OPEN

ProScan

®

 3 Series

6

.5

83

m

R

ESC

OK

ESC

OK

Button Description & Function

The removable display comprises a visual LCD dot matrix display with 4 separate push buttons. The bar graph at the right 

side of the display indicates the current level reading relative to the span - the distance between the 4mA | Empty and the 

20mA | Full

Exit Programming Mode
Return to a previous
Display Echo Curve

Digits Edit
Select Display Mode

Digits Edit
Select Display Mode

Enter Main Menu
Confirm Edit

Display Introduction

8

2

4-0167

     © Icon Process Controls Ltd.

Continuous Radar Level Sensor (80GHz)

ProScan

®

 3 Series

Measuring the tank is one of the most important aspects in configuring the sensor. When measuring the tank, take into account the 

location of the sensor with respect to fittings, risers, dome tops and bottoms, and identify where the measurements are taken from 

the sensor.

Programming Display

The  Range  is  the  overall  distance  from  the 

tip 

of the Sensor

 

to the Lowest Liquid level 

Min Configuration = 4mA setting.
With flat bottom tanks, the Range

and Empty Configuration values can be 

the same.

100%

Measurement

Location

0%

1.

Max Configuration = 20mA setting.

The distance from the tip of the sensor to the 

highest liquid or full level

2.

a)
b)

Range

Max Config

20 mA

4 mA

Summary of Contents for LevelPro ProScan 3 Series

Page 1: ...ual carefully before starting to use the unit Producer reserves the right to implement changes without prior notice Operating Manual Continuous Radar Level Sensor 80GHz ProScan 3 Series 24 0167 Icon P...

Page 2: ...ositioning Programming Display Display Introduction Basic Setup Connection Bluetooth Device to ProScan 3 Device Unit Settings Basic Parameters Settings Dimensions Warranty Returns Limitations 03 03 04...

Page 3: ...head fitting or having the sensor subject to the conditions inside the tank Safety Information Product Description De pressurize and vent system prior to installation or removal Confirm chemical compa...

Page 4: ...PP Transducer Weight 280g 316 SS PC Body PP Transducer 770g Installation Mounting Bracket Technical Specifications Working Principle The ProScan 3 80GHz radar is a transmitter for continuous level me...

Page 5: ...ith federal state provincial and local codes Note Remember that the output voltage of the power supply can be lower under nominal load with a sensor current of 20 5 mA or 22 mA and or with the additio...

Page 6: ...3 04 05 06 07 08 09 10 11 12 13 TVL Displays ProScan 3 Blind to TVL Display Connection Red wire Terminal 8 Black wire Terminal 11 Power Supply 120VAC Terminal 1 2 01 02 03 04 05 06 07 08 09 10 11 12 1...

Page 7: ...an be detected by the sensor Ensure that the radar signal strikes the surface of the liquid at a 90 angle Use the bubble level toensure 90 degree position of the sensor Consider Dead band while instal...

Page 8: ...ocess Controls Ltd Continuous Radar Level Sensor 80GHz ProScan 3 Series Measuring the tank is one of the most important aspects in configuring the sensor When measuring the tank take into account the...

Page 9: ...s 20ma Blind 0 9000 05 mm mm mm Basic Setup Blind 10 ShowType Level Damping Time 10 mm Basic Setup Damping Time 10 DeviceID 1 BaudRate 9600 Basic Setup OK OK Press Key OK Press Key OK OK OK Select Bas...

Page 10: ...2124 8 771 29 82 0 2023 11 21 16 29 36 Home Curve Set Update Time 23LD12184 Home Level inch Distance inch Current mA Percentage Running State 35 7873 84 2124 8 771 29 82 0 2023 11 21 16 29 36 Home Cur...

Page 11: ...Amount inch 4mA Location inch 20mA Location inch Blind Area inch Damping Time Device Address Baud Rate 120 00 0 0 0 0 119 9998 4 0157 50 1 9600 READ SET BACKUP RESTORE Home Curve Set 23LD12184 Set Ba...

Page 12: ...ing Time Device Address Baud Rate 120 00 0 0 0 0 110 00 4 00 10 1 9600 READ SET BACKUP RESTORE 100 Measurement Location 0 Range Max Con g 20 mA 4 mA Home Curve Set 23LD12184 Set Basic Parameters Advan...

Page 13: ...d to electrical mechanical or chemical damage due to improper accidental or negligent use 3 Have been modified or altered 4 Anyone other than service personnel authorized by Icon have attempted to rep...

Page 14: ......

Reviews: