CAN-8124/CAN-8224/CAN-8424 User Manual
CAN-8124/ CAN-8224/ CAN-8424 User Manual (Version 2.0, Aug/2007)
18/153
The lower rotary switch handles the CAN-8124/CAN-8224
/CAN-8424
data
rate (baud rate). The relationship between the rotary switch value and the
practical baud rate is displayed in the following table.
Table 2-7
Rotary Switch Value
Baud rate (K BPS)
0 125
1 250
2 500
For example, the setting data rate is 125 Kbps as in figure 2-6.
Figure 2-6 NA rotary switches
Note: If the “DR” rotary switch for the CAN-8x24 is set to ‘9’, the CAN-8x24 will
get into its initial mode. The DeviceNet firmware built in the CAN-8x24 will not
be executed. Before users employ the utility tool to configure the CAN-8x24,
the initial mode is needed. Because the CAN-8124/CAN-8224 has no RS-232
COM Port, it is necessary to run this utility tool in the off-line mode if users
want to get the EDS file of users’ CAN-8124/CAN-8224.
Furthermore, when the CAN-8124/CAN-8224/CAN-8424 is started up, the
DeviceNet firmware will check these rotary switches. Any illegal value on these
rotary switches will cause the CAN-8124/CAN-8224/CAN-8424 to fail when
booting-up.
Note: If users set the illegal values of the rotary switch, the MOD led would
flash when powering up. In this condition, users must configure the legal
values for the switches and reset the device, and then the device will work
normally.