A-10. CL-211 / CL-211-E DCON Command Sets
- 138 -
Command
Description
@AARHN
Read channel high latched value of analog input
N = 0 for CO
In 1ppm,
1 for PM2.5 in 1 ug/m3,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AARHCN
Read high alarm limit of an AI channel
N = 0 for CO
In 1ppm,
1 for PM2.5 in 1 ug/m3,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AARL
Read all low latched values of analog input channels
response
>(CO in 1 ppm)(relative humidity in 0.01%)(temperature in
0.01°C)(temperature in 0.01°F)(dew point temperature in
0.01°C)(dew point temperature in 0.01°F)
@AARLN
Read channel low latched value of analog input
N = 0 for CO
In 1ppm,
1 for PM2.5 in 1 ug/m3,
2 for relative humidity in 0.01%,
3 for temperature in 0.01°C,
4 for temperature in 0.01°F,
5 for dew point temperature in 0.01°C,
6 for dew point temperature in 0.01°F
@AARLCN
Read low alarm limit of an AI channel
N = 1 for relative humidity in 0.01%,
2 for temperature in 0.01°C,
3 for temperature in 0.01°F,
4 for dew point temperature in 0.01°C,
5 for dew point temperature in 0.01°F