C-6. CL-206-E Modbus Address Mappings (Base 1)
- 181 -
C-6. CL-206-E Modbus Address Mappings (Base 1)
Address Description
Attribute
30001 ~
30006
40001 ~
40006
Analog input value of channel 0 to 5. channel 0: H
2
S in 1ppm,
channel 1: relative humidity in 0.01%, channel 2: temperature in
0.01°C, channel 3:temperature in 0.01°F, channel 4: dew point
temperature in 0.01°C, channel 5: dew point temperature in 0.01°F
R
40225 ~
40230
High alarm limit of channel 0 to 5, channel 0: H
2
S in 1ppm, channel
1: relative humidity in 0.01%, channel 2: temperature in 0.01°C,
channel 3:temperature in 0.01°F, channel 4: dew point
temperature in 0.01°C, channel 5: dew point temperature in 0.01°F
R/W
40235 ~
40238
Low alarm limit of channel 1 to 5, channel 1: relative humidity in
0.01%, channel 2: temperature in 0.01°C, channel 3:temperature
in 0.01°F, channel 4: dew point temperature in 0.01°C, channel 5:
dew point temperature in 0.01°F
R/W
40272
Modbus NetID
Only for Modbus TCP protocol
R/W
30301
40301
Number of the digital input channels
Only for Modbus TCP protocol
R
30311
40311
Number of the digital output channels
Only for Modbus TCP protocol
R
30321
40321
Number of the analog input channels
Only for Modbus TCP protocol
R
30331
40331
Number of the analog output channels
Only for Modbus TCP protocol
R
30352
40352
Firmware version in hex format
Only for Modbus TCP protocol
R
40449
H2S offset in 1 ppm
R/W
40450
Relative humidity offset in 0.01%
R/W
40451
Temperature offset in 0.01°C
R/W
40481
Firmware version (low word)
R
40482
Firmware version (high word)
R
40483
Module name (low word), 0x0206
R
40484
Module name (high word), 0x434C
R
40485
RS-485 module address, 1 to 247
Only for Modbus RTU protocol
R/W