C-12. CL-213 / CL-213-E Modbus Address Mappings (Base 1)
- 218 -
Address Description
Attribute
00305 ~
00312
High alarm status of channel 0 to 7. Write 1 to clear high latched
alarm.
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W
00321 ~
00328
Enable/disable alarm of channel 0 to 7, write 0 to disable alarm ;
write 1 to enable alarm.
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W
00337 ~
00344
Alarm type, momentary or latched, of channel 0 to 7, write 0 to
enable momentary alarm mode; write 1 to enable latched alarm
mode.
channel 0: CO in 1ppm,
channel 1: CO
2
in 1ppm,
channel 2: PM2.5 in 1ug/m
3
,
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W