  A: ModbusMasterToolPC                                                                  Version 1.2.0 Jun 2023   

- 55 - 

Appendix A: ModbusMasterToolPC 

ModbusMasterToolPC is a free, easy-to-use tool for Modbus communication and 

diagnosing the wiring.   

Download and install the ModbusMasterToolPC 

http://ftp.icpdas.com/pub/cd/iiot/utility/modbusmastertoolpc/

 

This section intends to guide the steps for creating the Modbus communication with 

DL-100S-E logger. 

      1. Launch the ModbusMasterToolPC.exe. 

      2. Select New in the File menu. 

           

 

      3. Input the file name and click on the Save button. 

 

Summary of Contents for DL-110S-E

Page 1: ...0S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 1 DL 100S E DL 101S E DL 110S E DL 120 E Illumination Temperature Humidity Dew Point Data Logger User Manual Version 1 2 0 Date Jun...

Page 2: ...sequent to the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no r...

Page 3: ...ion via RS 485 DL 110S E DL 120 E Only 32 4 1 Building the RS 485 Connection 32 4 2 AI tab 36 4 3 Logger Configuration 37 5 Monitoring via Mobile Devices 38 6 Utility to Get Manage Data Log 39 7 FAQ 5...

Page 4: ...d using a variety of communication interfaces including Ethernet and PoE meaning that the device can be easily integrated into existing HMI or SCADA systems and are easy to maintain in a distributed c...

Page 5: ...data from DL 100S E series module over a Wi Fi network anytime and anywhere The iAir App can link to the DL 100S E series modules by specifying IP addresses or by searching all the modules connected t...

Page 6: ...er Ethernet PoE The DL 100S E series module features true IEEE802 3af compliant classification Class 1 PoE technology that allows both power and data to be carried over a single Ethernet cable PoE pro...

Page 7: ...Measurement Range 0 to 100 RH Resolution 0 1 RH Accuracy Typical 3 RH 20 80 RH refer to figure 1 LCD LED Display LCD Information Displayed Temperature C and F Humidity RH Relative Humidity Date and T...

Page 8: ...minal 12 to 48 VDC Powered via PoE IEEE 802 3af Class 1 require a PoE switch or injector Power Consumption PoE 0 7 W Max 0 7 W Max 1 2 W Max Non PoE 0 6 W Max 1 1 W Max Mechanical Dimensions W x L x H...

Page 9: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 9 2 2 Appearance...

Page 10: ...or a non PoE switch Installing a waterproof attachment on an RJ45 connector The DL 100S E series module is equipped with an RJ 45 waterproof connector that ensures the device is able to withstand pote...

Page 11: ...follow the procedure described below Step 1 Remove the RJ 45 Connector from the RJ 45 Cable Step 2 Feed the end of the two core power cable through the Sealing Nut Seal Lock Nut Clamp Ring and Gasket...

Page 12: ...Clamp Ring Step 6 Push the Seal Nut forward and Hand tighten it to seal the assembly Step 7 Insert the RJ 45 Cable into the RJ 45 Connector Step 8 Push the RJ 45 waterproof connector assembly forward...

Page 13: ...DL 120 E User Manual Version 1 2 0 Jun 2023 13 Step 10 Firmly tighten the connector to the module and ensure that it is completely connected Connector for Power Alarm Relay Output RS 485 Relay Output...

Page 14: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 14 2 3 Dimensions unit mm...

Page 15: ...d For connecting with a PC or a Android device Connecting to a PC or an Android device The DL 100S E series module can be connected to either a PoE network without a power source or to a non PoE netwo...

Page 16: ...ement of the subnet mask and the IP address for a device In other words take the device s IP address and set any bit positions that have a 0 in the subnet mask to 1 For example in an entire IPv4 subne...

Page 17: ...100S E series module logger eSearch is designed to search out the DL 100S E series logger connected on the same Ethernet network it supports for Linux and Windows and is needless to install The eSearc...

Page 18: ...al Version 1 2 0 Jun 2023 18 3 2 Logging into the DL 100S E 1 Enter the IP address for your DL 100S E in the address bar of a web browser 2 Type the Login password and click the Submit button The defa...

Page 19: ...ow Latched and maximum value High Latched logged Clicking on the Clear Low Latched button and the Clear High Latched button can reset the latched data to current value and latch new minimum or maximum...

Page 20: ...of the alarm modes is enabled the relay is linked to the alarm status for tapping audible visual alarm The Digital Output table is only available to the DL 101S E At the end of the page are the data t...

Page 21: ...m the Ethernet port Range 5 65535 unit second 0 Disable 180 Web Auto logout Sets the timeout for logout the web server in a logger when there is no any operation from the web browser interface Range 1...

Page 22: ...e update please refer to the section 7 FAQ Q4 3 5 MQTT MQTT stands for MQ Telemetry Transport it is a publish subscribe extremely simple and lightweight messaging protocol designed for constrained dev...

Page 23: ...to save the parameters Cycle sets the time period for update the publish messages in millisecond Module Topic Name sets the module topic name Relative Humidity Temperature C Temperature F Dew Point C...

Page 24: ...opic name of Module Topic Name Message Sub Topic Name or Module Topic Name Message Attribute Sub Topic Name Message Attribute Sub Topic Name sets the sub topic name for message attribute If a MQTT mes...

Page 25: ...r than the High Alarm Limit or lower than the Low Alarm Limit the alarm occurs until the measurement value is within a range from Low Alarm Limit to High Alarm Limit Latched If a measurement value hig...

Page 26: ...out timer for Ethernet communication if a host does not send a command over the setting time the Host Watchdog timeout occurs and the relay outputs the status set for Safe value The settings for Power...

Page 27: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 27 In this table it shows the settings for data logger All the settings take effect after clicking the Update Settings button...

Page 28: ...mory for data storage is full Over the upper limit of 600 000 No discards the new data default Yes overwrites the old data by new ones No Sampling Interval Sets the time interval for logging data It i...

Page 29: ...ssess the logger Filter Settings 1 Select the radio button for Add ___ ___ ___ ___ To The List and type the IP address for the accessible device in the following text box 2 Click on the Submit button...

Page 30: ...ction After setting the password for touch screen each time whoever wants to change to settings from the touch screed the password will be requested Change Web Password The password for logging into t...

Page 31: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 31 3 10 Logout Click the Logout on any page to logout the DL 100S E...

Page 32: ...nse Delay ms 0 4 1 Building the RS 485 Connection 1 Download the DCON Utility Pro from http ftp icpdas com pub cd iiot utility dcon_utility_pro 2 Launch the DCON_Utility_Pro exe If there are multiple...

Page 33: ...S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 33 3 Click the icon to configure the COM port 4 Select the COM Port number used to connect the DL 110S E logger 5 The Baud Rate is factory def...

Page 34: ...110S E DL 120 E User Manual Version 1 2 0 Jun 2023 34 6 Select the Protocol tab and check the protocol that set in the logger 7 Select the Format tab and check the parity that set in the logger 8 Clic...

Page 35: ...onfigure the logger Not e The Protocol Baud Rate Parity Checksum items marked with INIT means that when any of those items needs be modified the pin 4 INIT needs to be set in ON position and power cyc...

Page 36: ...2 AI tab In the AI form you can read the sensor readings such as ambient light humidity temperature and dew point temperature Humidity Adjust the Ambient Light offset Adjust the temperature offset C...

Page 37: ...E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 37 4 3 Logger Configuration In the Data Logger form you can change the data logger related settings Click on the Apply button to save the chang...

Page 38: ...data from DL 100S E series module loggers by entering a specific IP address or by performing an automatic search for available devices If a DL 100S E series module cannot be searched in the iAir App p...

Page 39: ...with timestamp download the logged data from a DL 100S E series logger and export the data to csv files for performing statistical analysis in Excel The iAir Utility can be obtained from https www ic...

Page 40: ...the Search New Device button to search the DL 100S E modules connected on the same Ethernet network 3 3 Check the checkbox next to a module and click the Add button to add the module in the utility 3...

Page 41: ...on the OK button Note Consult your network administrator before making changes to IP Address Mask Address Gateway 4 Get real time data trend chart and alarm event 4 1 Click the List icon to obtain th...

Page 42: ...the radio button for Temperature or Humidity to access the trend chart for those real time data check the checkbox next to each DL 100S E logger to display its trend chart or uncheck it to cancel dis...

Page 43: ...elect the System Settings on the Settings menu Set the Temperature Alert Value and Temperature Alarm Value for trigger events Check the checkbox next to The Record Time Everyday can schedule auto gene...

Page 44: ...023 44 5 Download data in a DL 300 logger and export the data 5 1 Select Update Database on the Settings menu 5 2 Click the Start button to download the data in DL 100S E modules 5 3 Click the close i...

Page 45: ...E DL 120 E User Manual Version 1 2 0 Jun 2023 45 5 4 Click the Query icon 5 5 Highlight the desired module set the Start Time and End Time and then click the Search button The data in the time period...

Page 46: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 46 5 6 Click the Export button to export the searched data in csv files for performing statistical analysis in Excel 6...

Page 47: ...n 1 2 0 Jun 2023 47 6 Group the devices by location or users 6 1 Select Group Settings on the Settings menu 6 2 Click the New button enter the group name and click the OK button in the pop up box and...

Page 48: ...on 1 2 0 Jun 2023 48 6 3 Select Device Settings on the Settings menu highlight the desired device and click the Edit Device button select the group name for the module and click the OK button in the p...

Page 49: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 49 6 4 Monitor the group data by clicking the Group icon and then highlighting the group name...

Page 50: ...efore clicking the submit button to save the IP setting and use after repowering Once any of those in the list is set only the device for which the IP address is saved in the list can assess the DL 10...

Page 51: ...Before updating the firmware ensure that the network settings for both your host computer and any DL 100S E modules are correctly configured or the update procedures via the Ethernet network may not f...

Page 52: ...User Manual Version 1 2 0 Jun 2023 52 Right click on the DL 100S E module name then select Firmware Update Select the firmware file and click on the Open button Make sure the IP address and MAC addre...

Page 53: ...mpt window will be displayed to show the progress Log in the DL 100S E web page Click on the Network tab then click on the Update button When it shows Complete 100 the update is finished You can close...

Page 54: ...DL 100S E DL 101S E DL 110S E DL 120 E User Manual Version 1 2 0 Jun 2023 54...

Page 55: ...and diagnosing the wiring Download and install the ModbusMasterToolPC http ftp icpdas com pub cd iiot utility modbusmastertoolpc This section intends to guide the steps for creating the Modbus commun...

Page 56: ...on 1 2 0 Jun 2023 56 4 Select Connect in the Connection menu 5 Select the communication interface When using TCP IP as the interface input the IP for your logger and click on the OK button 6 Select De...

Page 57: ...A ModbusMasterToolPC Version 1 2 0 Jun 2023 57 7 Select the Modbus Function code input the start address and length and click on the OK button 8 Read data...

Page 58: ...40311 Number of the digital output channels R 30321 40321 Number of the analog input channels R 30331 40331 Number of the analog output channels R 30352 40352 Firmware version in hex format R 40449 R...

Page 59: ...y date on LCD 0 100 R W 40805 Number of seconds in a cycle to display time on LCD 0 100 R W 40865 RTC year 2000 to 2159 R W 40866 RTC month 1 to 12 R W 40867 RTC date 1 to 31 R W 40868 RTC hour 0 to 2...

Page 60: ...od mode 2000 2159 R W 40888 Ending month when logging in period mode 1 12 R W 40889 Ending date when logging in period mode 1 31 R W 40890 Ending hour when logging in period mode 0 23 R W 40891 Ending...

Page 61: ...perature in 0 01 C channel 4 dew point temperature in 0 01 F R W 40233 40237 Low alarm limit of channel 0 to 4 channel 0 relative humidity in 0 01 channel 1 temperature in 0 01 C channel 2 temperature...

Page 62: ...second 0 to disable R W 40565 Module reset timeout value 30 to 65535 in second 0 to disable R W 40801 Number of seconds in a cycle to display temperature in Celsius on LCD 0 100 R W 40802 Number of se...

Page 63: ...the data logger sampling period 0 59 R W 40881 Starting year when logging in period mode 2000 2159 R W 40882 Starting month when logging in period mode 1 12 R W 40883 Starting date when logging in per...

Page 64: ...1 R W 00227 Write 1 to reload default TCP settings and reboot module W 00234 Write 1 to reboot module W 00280 Write 1 to clear all high latched analog input values W 00281 Write 1 to clear all low lat...

Page 65: ...s TCP protocol R W 30301 40301 Number of the digital input channels Only for Modbus TCP protocol R 30311 40311 Number of the digital output channels Only for Modbus TCP protocol R 30321 40321 Number o...

Page 66: ...0 255 in 0 1s Only for Modbus RTU protocol R W 40492 RS 485 host watchdog timeout count write 0 to clear Only for Modbus RTU protocol R W 30513 30519 40513 40519 High latched analog input value of cha...

Page 67: ...R 40873 The starting record to read log data low word R W 40874 The starting record to read log data high word R W 40875 The status of the data logging 0 stopped 1 running R 40876 The data logger com...

Page 68: ...y for Modbus TCP protocol W 00234 Write 1 to reboot module Only for Modbus TCP protocol W 00257 RS 485 Protocol 0 DCON 1 Modbus RTU Only for Modbus RTU protocol R W 00261 RS 485 host watchdog mode 1 e...

Page 69: ...us TCP protocol R 30321 40321 Number of the analog input channels Only for Modbus TCP protocol R 30331 40331 Number of the analog output channels Only for Modbus TCP protocol R 30352 40352 Firmware ve...

Page 70: ...input value of channel 0 to 1 R 30556 40556 Module reset status 1 power on 2 watchdog 3 software reset command Only for Modbus TCP protocol R 40558 Ethernet host watchdog timeout value 5 to 65535 in s...

Page 71: ...40879 Minute of the data logger sampling period 0 59 R W 40880 Second of the data logger sampling period 0 59 R W 40881 Starting year when logging in period mode 2000 2159 R W 40882 Starting month wh...

Page 72: ...nable 0 disable Only for Modbus RTU protocol R W 00270 Host watch dog timeout status write 1 to clear host watch dog timeout status Only for Modbus RTU protocol R W 00273 Reset status 1 first read aft...

Page 73: ...1 0 2019 Mar Added DL 110 E and DL 120 E information 1 1 1 2019 Apr Added Modbus register 40181 module alias name 1 1 2 2019 May Changed Modbus register 40181 module alias name to read only 1 1 3 2020...

Reviews: