ECAN-240-FD (Modbus TCP to 2-port CAN FD Gateway) User Manual
Version 1.0.0
Page
:
44
Copyright © 2022 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
5.1.1 Input Data Area
The “Input Data Area” including “CAN Rx FIFO”, “CAN Status” and “CAN Rx Buffer” information
for user to use Modbus Function Code 0x04 to get CAN/CAN FD messages and CAN status
from ECAN-240-FD.
Input Data Area of ECAN-240-FD
Protocol
Base Address
(0xxxx)
Description
00000 ~ 00399
CAN1 Rx FIFO Message #1 ~ #10
Reserved
00512 ~ 00519
CAN1 Status
Reserved
01024 ~ 01423
CAN1 Rx Buffer Message #0 ~ #9
Reserved
04096 ~ 04135
CAN2 Rx FIFO Message #1~ #10
Reserved
04608 ~ 04615
CAN2 Status
Reserved
05120 ~ 05519
CAN2 Rx Buffer Message #0 ~ #9
Reserved
08193 ~ 08194
Others:
Firmware version, rotary switch value…etc.