ECAN-240-FD (Modbus TCP to 2-port CAN FD Gateway) User Manual
Version 1.0.0
Page
:
56
Copyright © 2022 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
5.1.2.3 Others
“Others” information, including “Reboot system”, “Restore default setting” and “Clear CAN status”
of ECAN-240-FD module.
Others
Protocol
Base Address
(0xxxx)
PLC
Base Address
(4xxxx)
Words
Description
02049 ~ 02049
42050 ~ 42050
1
System Reboot
0x55AA: Reboot system
Others: do nothing
02050 ~ 02050
42051 ~ 42051
1
Restore default setting
0x55AA: Restore default
Others: do nothing
02051 ~ 02051
42052 ~ 42052
1
Clear CAN1 status
1: clear
Others: do nothing
02052 ~ 02052
42053 ~ 42053
1
Clear CAN2 status
1: clear
Others: do nothing