ECAN-240-FD (Modbus TCP to 2-port CAN FD Gateway) User Manual
Version 1.0.0
Page
:
58
Copyright © 2022 ICP DAS Co., Ltd. All Rights Reserved E-mail: service@icpdas.com
Appendix A. Troubleshooting
A.1.
How do I restore the web password for the module to the factory default
password?
The instructions below outline the procedure for resetting the web password to the factory default
value.
Note:
Be aware that ALL settings will be restored to the factory default values after the module is reset.
Step 1
Locate the SW1/SW2 switch that can be found on the top side of the ECAN-240-FD module and
set SW2 to
“F”
and SW1 to
“E”
position. Reboot the module to
load factory default settings
including default web password.
Step 2
Execute either the eSearch Utility to search for any ECAN-240-FD modules connected to the
network. Verify that the ECAN-240-FD has been reset to the original factory default settings. For
example, the module should be shown as having the default IP address, which is 192.168.255.1.