Step 4:
The parameters of the 0xF008 object handles the save procedure.
1.
Scroll to the end of the "CoE-Online" list and expand the tree view of the
0xF008 object
2.
Enter the value 0x12345678 for the "Code Word"
3.
Set the "Save configuration data" from FALSE to TRUE in order to save the
configuration data to the internal EEPROM. The parameter "Save error
encountered" (F008:05) indicates whether an error occurred during the
save process.
4.
In order for the configuration data to be loaded after a device restart set
the "Load factory default" to FALSE. It is always possible to return to the
factory default setting by setting this value back to TRUE.
5.
The "Save Counter" (F008:02) shows how often configuration data has
been stored to the local memory in the lifetime of the device.
ATTENTION:
The local memory only supports a limited number of save operations.
Depending on the memory version once the save operation exceeds
10000 cycles it can no longer be guaranteed that data are reliably saved
or are still readable. Therefore the "Save configuration data" (F008:04)
and the "Load factory default" (F008:03) should not be continuously set
from the controlling application program.