background image

 

 

 

Step2

Follow these steps 

“[Main Menu]

[Device]

[Download]

 to open the FW download window. 

Key in the MAC address we found in Step1, and an available IP address on this window. Select the 

firmware file (e.g. GW7472_v2.dat) to download. 

 

 

 

 

 

 

 

 

Step3

After downloading the firmware, please check the Utility whether the version is V2.0 or not on 

the Main Menu. 

 

 

Summary of Contents for GW-7472

Page 1: ...ICP DAS GW 7472 FAQ FAQ Version 3 1 ICP DAS Co Ltd 2014 10 13...

Page 2: ...g function 3 Q3 How to make a Class1 connection with the GW 7472 Utility Diagnostic window 4 Q4 Why did the pop up message FW Version Error be shown after I run the new version Utility 5 Q5 How to con...

Page 3: ...I O connection methods 1 Transport and trigger Exclusive Owner Cyclic 2 Original to Target Type POINT2POINT MULTICAST not supported 3 Target to Original Type POINT2POINT MULTICAST Q2 In some case the...

Page 4: ...t input size in the Forward Open Class1 Behavior on the Diagnostic window Please notice that the total input output size on the Diagnostic window and the total input output size on the Configuration w...

Page 5: ...ror be shown after I run the new version Utility A4 The utility of version 2 0 and later only supports the firmware version 2 0 and the after Please go to the product page of the GW 7472 to get the ne...

Page 6: ...GW 7472 Utility configuration window to find out your MAC address on the top of Network Settings b In another way you can get your MAC address from the ARP list Follow the Start Menu Run cmd to open...

Page 7: ...download window Key in the MAC address we found in Step1 and an available IP address on this window Select the firmware file e g GW7472_v2 dat to download Step3 After downloading the firmware please c...

Page 8: ...The configuration software is RSLogix 5000 Please follow the steps below a Add a new Module and select ETHERNET MODULE b Configure the Module Properties window Please notice that the total input size...

Page 9: ...9...

Page 10: ...in the figure below Click Class3 to start the connection If the devices have been connected and receive the information from Modbus devices the common packet will show 00 If GW 7472 couldn t receive...

Page 11: ...ire connection interface is shown below The wire connections between Modbus masters and Modbus slaves must be follow the figure we show below For non isolated RS 422 485 ports you should connect all s...

Page 12: ...in the Modbus Request Command and fill out the Modbus device settings you want to connect with Then set the Server IP in the MBTCP Server Setting Please notice that the total input output size on the...

Page 13: ...bute Single you can configure MSG ladder element in your routine Please refer the steps to complete the configurations 1 Create input output tags and input data data The data type of tags are Message...

Page 14: ...14 2 Add a new routine 3 Add MSG element in your ladder and select input_tags...

Page 15: ...e select the Ethernet module in the PLC and click OK Now the name of the Ethernet module should be filled in at the Path here we also have to fill in the full path to GW 7472 in this example GW 7472 h...

Page 16: ...16 4 Add MSG element in your ladder and select Output_tags...

Page 17: ...tag and the Source Length should be 4 bytes Under Communication tab the Path should be the same as the one used to read data 5 This is a simple example that only will issue one read request in a norm...

Page 18: ...18 If you want to send Get Set Attribute Single continuously you can refer to the ladder below...

Reviews: