GW-7552 PROFIBUS/MODBUS GATEWAY Quick Start User Guide
(Version 1.00)
PAGE
:
4
Set the parameters of the GW-7552
The user just needs to change Modbus type to slave and use the default
value in the other parameters in this example. Please refer to user manual
section 4.3 The Configuration of the common parameters.
Click <Parameter Data>
button to enter the Parameter
Data dialog
Double click the GW-
7552’s icon to enter the
Slave configuration dialog
Step 4: Finish adding i-7550 in
the DP-master interface.
Step 3: Set address of GW-7552
and then click OK button.
Step 2: Choose GW-7552 device
and click Add button.
Step 1: Click insert slave button
in the PROFIBUS
configuration tool.