2.4. Rotary Switch
When users would like to update the module’s firmware or set the CAN baud rate,
message filter of the I-2533CS series, use the rotary switch on the upper of the power
connector to achieve this purpose. Users can find it on the top of the power connector.
Figure 2-4 Location of Rotary Switch
There are 16 sections on the rotary switch. They are described on the following
table.
Table 2-2 Description of Rotary Switch
Switch Value Description
0
Set baud rate to 10 kbps
1
Set baud rate to 20 kbps
2
Set baud rate to 50 kbps
3
Set baud rate to 80 kbps
4
Set baud rate to 100 kbps
5
Set baud rate to 125 kbps
6
Set baud rate to 250 kbps
7
Set baud rate to 500 kbps
8
Set baud rate to 800 kbps
9
Set baud rate to 1 Mbps
A
Set baud rate to user-defined baud rate which is configured
by I-2533CS utility.
B~D
N/A
E
Set I-2533CS into firmware update mode.
F
Set I-2533CS into configuration mode.
I-2533CS series CAN to Single Mode Fiber Bridge User Manual (version 1.0.0)
Page: 12