I-7242D user manual
I-7242D DeviceNet/Modbus RTU Gateway User’s Manual, July 2006, Version 1.1 90/124
2. Apply the Master’s Explicit Request Messages to set the Identify object.
The service ID (0x05) is reset service.
Master
(MAC
ID
=0x0A)
Slave
(MAC
ID
=0x09)
Slave (MAC ID =0x09) responses the shutdown message to network.
_ Group 2 Message
| _ Destination MAC ID=0x09
| | _ Message ID =4
| | | _ Frag=0. Transaction ID=0. Souce MAC ID= 0x0A
| | | | _ Service=Reset service
| | | | | _ Class ID=1
| | | | | | _ Instance ID=1
| | | | | | |
ID=10 001001 100. Data= 0A 05 01 01 00
_ Group 2 Message
| _ Source MAC ID=0x09
| | _ Message ID =3
| | | _ Frag=0. Transaction ID=0. Destination MAC ID= 0x0A
| | | | _ Service= Reset Response
| | | | |
| | | | |
ID=10 000011 011. Data= 0A 85
_ Group 2 Message
| _ Source MAC ID=0x09
| | _ Message ID =3
| | | _ Frag=0. Transaction ID=0. Destination MAC ID=9
| | | | _ Service code= 0x4E, Device Shutdwon message
| | | | | __ Class ID=1
| | | | | | _ Instance ID=1
| | | | | _|__ __|__ _____ Shutdown Code
ID=10 001001 011. Data= 0A CE 01 00 01 00 04 00