I - 7 5 5 0 E Q u i c k S t a r t
( V e r s i o n 1 . 0 0 , J u n e / 2 0 1 4 )
P A G E
:
2
PROFIBUS connection
Here we recommend users to
use the standard PROFIBUS
cable and connector (DB9
male). It is only needed to use
D-type connector via
PROFIBUS cable to connect
PROFIBUS Master station and
I-7550E module. PROFIBUS
Master station and I-7550E
module belong to terminal
equipments in this example, thus we need to enable the terminator resistor in
the D-type connector.
Address setting
The I-7550E is a slave device of PROFIBUS DP protocol. The station address of
I-7550E can be set by DIP switch. The DIP switch can be seen by open the
cover, as shown in the below. The range of DIP switch is 0~126, here we set I-
7550E module’s DIP switch to 1.
LED status indicator
LED
Status
Description
flash
When PWR led and ERR led are flashing at the same time,
which means there is system error in the I-7550E. Please contact
us for solution.
on
Power supply is ok.
The firmware has loaded.
PWR
off
Power supply has failed.
flash
When the I-7550E has diagnostic message, it will flash slowly
(flash once about 220ms).
on
The connection is error with PROFIBUS Master device or
PROFIBUS system configuration is not correct.
ERR
off
PROFIBUS system configuration is correct.
It is normal operation.
on
Data exchange mode.
It is normal operation.
RUN
off
I-7550E module is not in data exchange mode.
DIP switch (SW1)
Station
address
1 2 3 4 5 6 7 8
1
1 0 0 0 0 0 0 0
10
0 1 0 1 0 0 0 0
31
1 1 1 1 1 0 0 0
Note: 1=>ON, 0=>OFF