P3
2
Zero-Initialization setting
1. Connect the iXN-2VB3 to iWSN-100X-CLE or iWSN-101X-CLE.
(Hereinafter referred to as the transmitter)
2. Clear the zero-initialization setting first. (set the F1/F2 pin to
ON, then turn on the transmitter power)
3. Read the register of iWSN-200x, will get a value not close to
zero.
PLC
address
(Base1)
Protocol
address
(Base0)
Data
Data type
Description
40257
30257
256
(0x
01
00)
36
Uint16
Mean value: X
40258
30258
257
(0x
01
01)
18
Uint16
Mean value: Y
40259
30259
258
(0x
01
02)
94
Uint16
Mean value: Z
4. iXN-2VB3 is fixed at the location to be measured and kept flat
and still.
5. Make the zero-initialization setting. (Set F1 pin to ON / F2 pin to
OFF, then turn on the transmitter power)
Item
Name
Instructions
1
F1
F2
(Clear the
zero-initialization setting)
■:
ON
□:
OFF
2
PWR
ON
:
Power on
Item
Name
Instructions
1
F1
(zero-initialization
setting)
■:
ON
□:
OFF
F2
(zero-initialization
setting)
□:
ON
■:
OFF