P4 

6. After  successfully  reading  the  first  iWSN-200x  register  value, 

press  and  hold  the  Wake  button  for  more  than  1  second  to 
reset to zero. 

7. Read  the  iWSN-200x  register  and  confirm  that  the  value  is 

close to zero. 

PLC 

address 

(Base1) 

Protocol 

address 

(Base0) 

Data 

Data type 

Description 

40257 
30257 

256 

(0x

01

00) 

Uint16 

Mean value: X 

40258 
30258 

257 

(0x

01

01) 

Uint16 

Mean value: Y 

40259 
30259 

258 

(0x

01

02) 

Uint16 

Mean value: Z 

8. Turn off the zero-initialization setting. (set the F1/F2 pin to OFF, 

then turn off the transmitter power) 

9. Complete the zero setting, please turn on the power again for 

vibration measurement. 

10.  If  the  measurement  position  is  adjusted,  please  re-execute 

the  zero-initialization  procedure  to  ensure  the  measurement 
accuracy. 

 

PWR

 

ON

Power on     

 

Item 

Name 

Instructions 

Wake   

(zero-initialization 

setting) 

 

Item 

Name 

Instructions 

F1   

(Turn off the 

zero-initialization setting) 

□:

ON   

■:

OFF 

 

F2   

(Turn off the 

zero-initialization setting) 

□:

ON   

■:

OFF

 

PWR

 

OFF

Power off

     

 