M-7084 User Manual, Rev. A1.3 7PH-013-A13
38
Examples:
Command: $0103
Response: !0100010
Reads the channel 3 low pass filter time of module 01
and the module responds with 00010 which means 10
micro seconds.
Related Commands:
Section 2.5 $AA0N(data), Section 2.9 $AA4, Section 2.10
$AA4vv
Notes:
1.
The low pass filter time should be the same for channel 0
and 1. When it is set to either one of the channel 0 or 1,
both channels will be set to the same value.
2.
The low pass filter time should be the same for channel 2
and 3. When it is set to either one of the channel 2 or 3,
both channels will be set to the same value.
3.
The low pass filter time should be the same for channel 4,
5, 6 and 7. When it is set to either one of the channel 4, 5,
6 or 7, all of the 4 channels will be set to the same value.