M-7084 User Manual, Rev. A1.3 7PH-013-A13
108
2.41 ~AAI
Description:
The Soft INIT command is used to enable modification of the
Baud Rate and checksum settings using software only.
Syntax:
~AAI[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
I
Command to set the Soft INIT
Response:
Valid Response:
!AA[CHKSUM](CR)
Invalid Response:
?AA[CHKSUM](CR)
!
Delimiter character for a valid response
?
Delimiter character for an invalid response
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.
Examples:
Command: ~01I
Response: !01
Sets the soft INIT of module 01 and returns a valid
response.
Related Commands:
Section 2.1 %AANNTTCCFF, Section 2.45 ~AATnn