M-7084 User Manual, Rev. A1.3 7PH-013-A13
55
2.13 $AA6
Description:
Reads the start/stop counting status of each channel.
Syntax:
$AA6[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
6
Command to read the channel counting status
Response:
Valid Response:
!AAVV(VV)[CHKSUM](CR)
Invalid Response:
?AA[CHKSUM](CR)
!
Delimiter character for a valid response
?
Delimiter character for an invalid response
AA
Address of the responding module (00 to FF)
VV
A two-digit hexadecimal value, where bit 0
corresponds to channel 0, bit 1 corresponds to
channel 1, etc. When the bit is 1 it means that the
channel is counting and 0 means that the channel is
not counting.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the