2.14 $AA6N
Description:
Sets the counter value of a channel to preset value.
Syntax:
$AA6N[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
6
Command to clear the counter value
N
Specifies the channel to be cleared (0 ~ 7)
Response:
Valid command:
!AA[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the