M-7084 User Manual, Rev. A1.3 7PH-013-A13
75
2.24 @AABB
Description:
Reads the battery backup counter status of each channel.
Syntax:
@AABB[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
BB
Command to read the battery backup counter status
Response:
Valid Command:
!AAVV[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
VV
A two-digit hexadecimal value, where bit 0
corresponds to channel 0, bit 1 corresponds to
channel 1, etc. When the bit is 1 it means that the
battery backup counter is enabled for the channel
and 0 means that the battery backup counter is
disabled for the channel.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.