M-7084 User Manual, Rev. A1.3 7PH-013-A13
87
2.30 @AAFT
Description:
Reads the frequency measurement timeout setting.
Syntax:
@AAFT[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
FT
Command to read the frequency measurement
timeout setting
Response:
Valid Command:
!AAVV[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
VV
Two hexadecimal digits to represent the timeout
value in tenths of a second, for example, 01 denotes
0.1 seconds and FF denotes 25.5 seconds.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.