M-7084 User Manual, Rev. A1.3 7PH-013-A13
91
2.32 @AAGN
Description:
Reads the preset counter value of channel N.
Syntax:
@AAGN[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be set (00 to FF)
G
Command to read the preset counter value of a
channel
N
Specifies the channel to be read (0 ~ 7)
Response:
Valid command:
!AA(Data)[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
(Data)
The preset counter value in eight hexadecimal digits
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.