M-7018 8 Channel Analog Input Module- QuickStart (Dec/2017)
ICP DAS USA, Inc.
| 1-310-517-9888 | 24309 Narbonne Ave. Suite 200. Lomita, CA 90717
2
3. Block/ Wiring Diagram
4. Default Settings
Default settings for the M-7017, M-7018 and M-7019 series modules are:
▫
Protocol: Modbus RTU
▫
Module address: 01
▫
Analog input type:
Type 08, -10V to 10V, for the M-7017 and M-7019 series
Type 1B, -150V to 150V, for the M-7017R-A5
Type 0D, -20mA to +20mA for the M-7017C and M-7017RC
Type 05, -2.5V to 2.5V, for the M-7018 series
▫
Baud Rate: 9600 bps
▫
Filter set at 60Hz rejection (Not used by the M-7019R, firmware version B2.6 and
earlier)