3.6.3 Sub-function 05 (0x05) - Read the
Communication Protocol
This sub-function code is used to read the communication protocol currently
being used by the module.
Request
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0x46
02
Sub-function Code
1 Byte
0x05
03
Reserved
1 Byte
0x00
Response
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0x46
02
Sub-function Code
1 Byte
0x05
03
Reserved
1 Byte
0x00
04
Baud Rate
1 Byte
The Baud Rate code, see Section 1.9.1
for details.
05 - 07 Reserved
3 Bytes
0x00 0x00 0x00
08
Protocol
1 Byte
0: DCON
1: Modbus RTU
09 - 10 Reserved
2 Bytes
0x00 0x00
Error Response
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0xC6
02
Exception Code
1 Byte
03: Reserved bits should filled with zero,
or an incorrect number of bytes were
received
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...