3.6.6 Sub-function 08 (0x08) - Set the Analog
Input Type Code
This sub-function code is used to set the Type Code for a specific Analog Input
channel of a module.
Request
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0x46
02
Sub-function Code
1 Byte
0x08
03
Reserved
1 Byte
0x00
04
Channel Number
1 Byte
0x00 to 0x05
05
Type Code
1 Byte
The Type Code, see Section 3.6 for
details.
Response
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0x46
02
Sub-function Code
1 Byte
0x08
03
Type Code
1 Byte
0: OK
Others: Error
Error Response
00
Address
1 Byte
1 to 247
01
Function Code
1 Byte
0xC6
02
Exception Code
1 Byte
03: The Type Code is out of range, the
channel number is out of range,
reserved bits should be filled with
zero, or an incorrect number of
bytes were received
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...