Execute “FW_Update_Tool.exe” with the administrator privileges ( ) and follow the steps
as Figure 5.3:
In "Download Interface", select a network port for connecting to MDC-211-WF.
In "Firmware Path", select the latest firmware update file (MDC211WF_xxxx.fw).
In "Firmware Update", click “Update” to start the firmware updating.
(4)
When the update is completed, “Update OK” will be displayed in the “FW_Update_Tool”
window to indicate that the firmware updating is successful. Next, remove the short
connection between FW and P.GND, and reboot the power supply, then check the current
firmware version on the Web interface.