PM
-
3133 User
’s Manual v1.09
Last Revised: Jun. 2021 Page: 24
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: service@icpdas.com
6.2.2 Modbus Register
Modbus Module #1
– Coil: Relay Value
Parameter name
Modbus Register
Len
Data
Type
Range
Default
value
Comment
Modicom
Format
Hex
DO 0
04097
0x1000
Word
Byte
0 = OFF
1 = ON
0
DO 1
04098
0x1001
Word
Byte
0 = OFF
1 = ON
0
DO 0
Power On Value
04113
0x1010
Word
Byte
0 = OFF
1 = ON
0
DO 1
Power On Value
04114
0x1011
Word
Byte
0 = OFF
1 = ON
0
Modbus Module #2
– Holding Register : System Parameter Setting
Parameter name
Modbus Register
Len
Data
Type
Range
Default
value
Units
Comment
Modicom
Format
Hex
PT_Ratio
44100
0x1003
Word
UInt
1-65535
100
0.01
CT_Ratio
44101
0x1004
Word
UInt
1-65535
1
Wiring Mode
44107
0x100A Word
UInt
1: 1P2W
2: 1P3W
3: 3P3W2CT
4: 3P3W3CT
5: 3P4W3CT
5
Only work
when
SW9-SW10 is
all off
Set Energy to Zero 44108
0x100B Word
UInt
0x0055
Only Write
Reset to Factory
Settings
44109
0x100C Word
UInt
0x0055
Only Write
Default Frequency
44110
0x100D Word
UInt
0x0055: Auto
0x0064: 50Hz
0x0078: 60Hz
0x0055
Re-power the
module after
setting
Energy
Absolute
Accumulated Mode
44113
0x1010 Word
UInt
0: Enable
1: Disable
0