PM
-
3133 User
’s Manual v1.09
Last Revised: Jun. 2021 Page: 25
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: service@icpdas.com
Harmonic Phase
Select
44114
0x1011 Word
UInt
0: Disable
1: Phase A
2: Phase B
3: Phase C
0
Display Voltage
44115
0x1012 Word
UInt
0: Automatic
1: Show as Vln
2: Show as Vll
0
Refer to Q12
Modbus Module #3
-
Input Register : System Information
Parameter name
Modbus Register
Len
Data
Type
Range
Default
value
Units
Comment
Modicom
Format
Hex
Wiring Type
30513
0x0200
Word
UInt
9: 1P2W
10: 1P3W
11: 3P3W2CT
12: 3P3W3CT
13: 3P4W
14: 3P3W2CT
(HW)
15: 3P3W3CT
(HW)
16: 3P4W
(HW)
13
(HW)
:
set
wiring by
hardware Dip
Switch
Phase Sequence
30514
0x0201
Word
UInt
0: Negative
(ACB)
1: Positive
(ABC)
Only work
when 3P4W
Model Name
30515
0x0202
Word
UInt
3133: PM-3133 3133
Model Type
30516
0x0203
Word
UInt
0x0001: 50Hz
0x0002: 60Hz
0x0002
Firmware Version
30517
0x0204
Word
BCD
0x0100
Ver. 1.0