8.3.3 Store and Restore Object
The users can write the object the value 65766173h to object with index 1010h and
subindex 1 to save the application setting, or write the value 64616F6Ch to object with
index 1011h and subindex 1 and reboot the module to load the factory default. The
following table lists the relative objects which will be stored or restored after writing
these two objects:
Index
Subindex Description
2010h
1
DO power on value
1800h
1~5
TxPDO1 parameter
……
……
……
1813h
1~5
TxPDO1 parameter
Note:
For power meter system parameters setting, such as object 320Bh, users need
write object index 320Ch subindex 02h to 55h to load the factory default setting.