Tiny Serial-to-Ethernet Device Server
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-64 -
The following is an overview of the parameters contained in the
Port1 Settings
section:
Item
Description
Default
Interface Settings
Interface
This parameter is used to set the interface mode (Loopback, RS-
232, RS-422 or RS-485) of serial port
for the tDS-718i-D only
.
Loopback:
the internal loopback is used to self-testing.
RS-232
Pull-High/Low Resister
This parameter is used to enable or disable
pull-high/low resister
for RS-485 or RS-422 of the tDS-718i-D only (1K Ohm)
.
Disable
Terminal Resister
This parameter is used to enable or disable terminal
resister
for
RS-485 or RS-422 of t the tDS-718i-D only (120 Ohm)
.
Disable
Port Settings
Baud Rate (bps)
This parameter is used to set the Baud Rate for the COM ports.
115200
Data Size (bits)
This parameter is used to set the Data Size for the COM ports.
8
Parity
This parameter is used to set the Parity for the COM ports.
None
Stop Bits (bits)
This parameter is used to set the Stop Bits for the COM ports.
1
Flow Control
This parameter is used to set the Flow Control for the COM
ports.
None
Allow Driver Control
Enable client (VxComm Driver) to dynamically change the data
format and baud rate settings.
Enable
Operation Mode
M0/Multi-echo
: Share received serial data between clients.
M1/Single-echo
: Send received serial data to the requested
client only.
0 = Data-sharing;
1 = Non-sharing
0
Local TCP Port
TCP Command Port +1
Note:
COM1/COM2/COM3 = TCP port 10001/10002/10003
10001
Connection Idle (seconds)
If the Local TCP port does not receive any data via the TCP/IP for
a certain period, the tDS-700/DS-2200 will disconnect the socket
based on the TCP timeout value.
Settings range: 1 ~ 65535 (seconds);
Disabled: 0;
180
Prefix String
This parameter is used to set the first character in a line of data.
Settings range: Max. 8 chars.
N/A